T1641100 Red Lion Controls, T1641100 Datasheet - Page 13

PID TEMPERATURE CONTROLLER, ANALOG

T1641100

Manufacturer Part Number
T1641100
Description
PID TEMPERATURE CONTROLLER, ANALOG
Manufacturer
Red Lion Controls
Type
Temperaturer
Datasheets

Specifications of T1641100

Thermocouple Type
T, E, J, K, R, S, B, N, C, Linear MV
Operating Temperature Max
50°C
Operating Temperature Min
0°C
Output Voltage Max
10VDC
Output Voltage Min
0V
Accuracy
0.3%
Approval
RoHS Compliant
Brand/series
T16 Series
Dimensions
49.5mmW×49.5mmH×115.3mmD
Enclosure Rating
IP65
Input Type
RTD/Thermocouple
Ip Rating
IP65
Memory
EEPROM
Mounting Type
Panel
Output Type
Analog
Power, Rating
8 VA
Primary Type
Controller
Special Features
EEPROM
Standards
cURus, CE
Termination
Screw
Voltage, Supply
85 to 250 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
arrow keys. To allow the P16 to “learn” the signal, use the Applied Method. For
Applied Method, press !. The ° annunciator is turned on to indicate the
applied method. Adjust the applied signal level externally until the appropriate
value appears under INP2. Using either method, press " to store the value for
INP2. (The controller can be toggled back to the Key-in Method by pressing !
before ".)
setting range of the setpoint. Set the limit so that the setpoint value cannot be
set below the safe operating area of the process.
setting range of the setpoint. Set the limit so that the setpoint value cannot be
set above the safe operating area of the process.
SELECTION
available only on models with alarms), when the User terminal 1 is connected
(pulled low) to Common terminal 8.
No Function: No function is performed.
Program Lock: The Configuration Loop is locked, as long as activated
Integral Action Lock: The integral action of the PID computation is disabled
Auto/Manual Select: This function selects (maintained action) Automatic
Setpoint 1 or 2 Select: This function selects (maintained action) Setpoint
Setpoint Ramp Disable: The setpoint ramping feature is disabled, as long as
Reset Alarms: Active alarms are reset, as long as activated (maintained action).
20. 0 0
999. 9
NONE
PLOC
ILOC
trnF
INP2
For Key-in Method, enter the second coordinate Input Value by using the
SPLO
The controller has a programmable low setpoint limit value to restrict the
SPHI
The controller has a programmable high setpoint limit value to restrict the
InPt
PLOC
The controller performs the selected User Input function (User Input
(maintained action).
(frozen), as long as activated (maintained action).
(open) or Manual Control (activated).
1(open) or Setpoint 2 (activated) as the active setpoint.
activated (maintained action). Any time the user input is activated with a
ramp in process, ramping is aborted.
Active alarms are reset until the alarm condition is cleared and triggered
again (momentary action).
"' "
No Function
Program Lock
Integral Action Lock
Auto/Manual Select
0. 0 0
0. 0 0
-999
-999
FUNCTION
USER INPUT FUNCTION (OPTIONAL)
INPUT VALUE SCALING POINT 2
to
to
to
to
20. 0 0
10. 0 0
SETPOINT HIGH LIMIT
SETPOINT LOW LIMIT
9999
9999
SELECTION
mA
V
SPrP
ALrS
SPt
Setpoint 1 or 2 Select
Setpoint Ramp Disable
Reset Both Alarms
FUNCTION
13
SELECTION
while in the Display Loop. In any other loop or module location, pressing !
will perform an escape to the Display Loop.
No Function: No function is performed.
Auto/Manual Select: This function toggles (momentary action) the controller
Setpoint 1 or 2 Selection: This function toggles (momentary action) the
Reset Alarms: This function can be used to reset one or both of the alarms
NONE
trnF
F1In
NONE
The controller performs the selected F1 key function, when ! is pressed
between Automatic and Manual Control.
controller between Setpoint 1 and Setpoint 2.
when activated (momentary action). The alarm will remain reset until the
alarm condition is cleared and triggered again.
SPt
No Function
Auto/Manual Select
Setpoint 1 or 2 Select
FUNCTION
F1 KEY FUNCTION
SELECTION
A1rS
A2rS
ALrS
Reset Alarm 1
Reset Alarm 2
Reset Both Alarms
FUNCTION