Specifications of 70/00382108

Thermocouple Type
L, J, U, T, K, N, S, R, B
Operating Temperature Max
55°C
Operating Temperature Min
0°C
Output Voltage Max
250VAC
Output Voltage Min
5V
Approval Bodies
FM, UL
Technical data
Thermocouple input
Resistance thermometer input
Standard signal input
Measurement circuit monitoring
09.02/00357838
M. K. JUCHHEIM GmbH & Co • 36035 Fulda, Germany
Designation
Fe-Con
Fe-Con
Cu-Con
Cu-Con
NiCr-Ni
NiCrSi-NiSi
Pt10Rh-Pt
Pt13Rh-Pt
Pt30Rh-Pt6Rh B
Cold junction
Designation
Pt 100
Pt 1000
KTY11-6
Sensor lead resistance
Measurement current
Lead compensation
Designation
Voltage
Current
Transducer
Thermocouple
Resistance thermometer
Voltage
Current
1. In the event of a fault, the outputs move to a defined status (configurable).
= factory setting
1.
for Type 702040/41 with 2 relay outputs (option)
2—10V / 0.2—1V
0—10V/ 0—1V
4—20mA
0—20mA
J
U
T
K
N
S
R
L
EN 60 751
EN 60 751
EN 60 584
EN 60 584
EN 60 584
EN 60 584
EN 60 584
EN 60 584
EN 60 584
• recognised
1
Range
Range
0 — 10V, input resistance R
2 — 10V, input resistance R
0 — 1V, input resistance R
0,2 — 1V, input resistance R
4 — 20mA, voltage drop 1V max.
0 — 20mA, voltage drop 1V max.
Overrange/
underrange
Connection type
2-/3-wire
2-/3-wire
2-wire
Not required for 3-wire circuit. For 2-wire circuit, lead compensation can be implemented
in software through process value correction.
-200 to + 900°C
-200 to +1200°C
-200 to + 600°C
-200 to + 400°C
-200 to +1372°C
-200 to +1300°C
0 —
0 —
0 —
- not recognised
1820 °C
1768°C
1768°C
Probe /lead short-circuit
20 max. per lead for 2- and 3-wire circuit
Range
-200 to +850°C
-200 to +850°C
E
-50 to +150°C
E
E
E
> 10M
> 10M
> 100k
> 100k
1
Pt 100 internal
1
-
-
-
250µA
Measurement
accuracy
Measurement
accuracy
Measurement
accuracy
Data Sheet 70.2040
0.4%
0.4%
0.4%
0.4%
0.4%
0.4%
0.4%
0.4%
0.4%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
1.0%
1
Probe/lead break
Ambient
temperature error
100 ppm/°C
100 ppm/°C
100 ppm/°C
100 ppm/°C
100 ppm/°C
100 ppm/°C
100 ppm/°C
100 ppm/°C
100 ppm/°C
Ambient
temperature error
50 ppm/°C
50 ppm/°C
50 ppm/°C
Ambient
temperature error
100 ppm/°C
100 ppm/°C
100 ppm/°C
100 ppm/°C
100 ppm/°C
100 ppm/°C
-
-