E5CN-QMT500-AC100240 Omron, E5CN-QMT500-AC100240 Datasheet - Page 6

Temperature Controller

E5CN-QMT500-AC100240

Manufacturer Part Number
E5CN-QMT500-AC100240
Description
Temperature Controller
Manufacturer
Omron
Datasheet

Specifications of E5CN-QMT500-AC100240

Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Temperature Accuracy ±
0.1%
Output Voltage Max
240VAC
Output Voltage Min
10.2V
Supply Voltage Ac, Min
100V
Thermocouple Type
J, K, T, E, L, U, N, R, S, B, W, PLII
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Specifications
Ratings
Power supply voltage
Operating voltage range
Power
consump-
tion
Sensor input
Input impedance
Control method
Control
outputs
Auxiliary
outputs
Event
inputs
External power supply for ES1B 12 VDC ±10%, 20 mA, short-circuit protection circuit provided
Setting method
Indication method
Multi SP
Bank switching
Other functions
Ambient operating temperature −10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C
Ambient operating humidity
Storage temperature
E5CN
E5CN-U
Relay output
Voltage output
(for driving SSR)
Current output
Long-life relay
output
Number of outputs 1 or 2 max. (Depends on the model.)
Output
specifications
Number of inputs
External contact
input
specifications
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
100 to 240 VAC: 7.5 VA (max.) (E5CN-R2T at 100 VAC: 3.0 VA)
24 VAC/VDC: 5 VA/3 W (max.) (E5CN-R2TD at 24 VAC: 2.7 VA)
100 to 240 VAC: 6 VA (max.)
24 VAC/VDC: 3 VA/2 W (max.) (models with current output: 4 VA/2 W)
Models with temperature inputs
Models with analog inputs
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.)
ON/OFF control or 2-PID control (with auto-tuning)
E5CN
E5CN-U
E5CN
E5CN-U
E5CN
E5CN
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum
applicable load: 5 V, 10 mA
2
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
Digital setting using front panel keys
11-segment digital display and individual indicators (7-segment display also possible)
Character height: PV: 11 mm, SV: 6.5 mm
Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial
communications.
Not supported
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout
detection (including SSR failure and heater overcurrent detection), 40% AT, 100% AT, MV limiter, input
digital filter, self-tuning, temperature input shift, run/stop, protection functions, control output ON/OFF
counter, extraction of square root, MV change rate limit, logic operations, PV/SV status display, simple
program, automatic cooling coefficient adjustment
25% to 85%
−25 to 65°C (with no condensation or icing)
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Voltage input: 0 to 50 mV
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable
load: 5 V, 10 mA
SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load:
5 V, 10 mA
Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection
circuit
4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, load power supply
voltage: 75 to 250 VAC (DC loads cannot be connected.), minimum applicable load: 5 V, 10 mA,
leakage current: 5 mA max. (250 VAC, 60 Hz)
E5CN/E5CN-U
6

Related parts for E5CN-QMT500-AC100240