4-4-4
4-4-5
Baud Rates
Terminating Resistance
Note
Note Set the same baud rate for all the nodes on the Network. Normal communica-
2. Do not set the same node address twice within the same Network. An error
3. The send sequence for the data link areas is determined according to the
4. Assign node addresses consecutively beginning from 01 whenever possi-
Set the following pins for the baud rate setting (DIP switch).
1. Always turn OFF the PLC’s power before setting the baud rate.
2. Keep pins 3 and 4 set to OFF. If they are turned ON, internal data may be
Set the same baud rate for all the nodes on the Network using DIP switch pins
1 and 2 on the front of the Unit. The baud rate is set as shown below.
The maximum transmission distance will also change according to the setting.
tion cannot be performed unless the same baud rate is set for all the nodes.
Turn ON the terminating resistance using the switch on the bottom of the Unit
for the Units of both ends of the Network. The terminating resistance is
required at both ends of a Network to absorb unnecessary signals and reduce
noise.
The Controller Link Unit has built-in terminating resistance, which can be con-
nected simply by turning ON the slide switch.
OFF
ON
OFF
ON
OFF (factory default)
ON
will occur if the same address is set for two different nodes. The ERC indi-
cator on the front of the Unit will light and either communications will stop,
or the INS indicator will not light and you will be unable to participate in the
Network.
sequence of node addresses for automatically set data links.
ble to minimize Network construction time.
erased.
Note The factory default setting is shown in bold.
Switch at the front
Pin 1
Switch
The factory default setting is shown above.
OFF
OFF
ON
ON
ON
Pin 2
Not connected.
connected
Pin 1, 2: Baud rate
Pin 3, 4: Not used (must be OFF)
2 Mbps
1 Mbps
500 Kbps
Do not set.
ON
Baud rate
Terminating resistance
500 m
800 m
1 km
transmission distance
Maximum
Section 4-4