CPM1A-10CDR-A-V1 Omron, CPM1A-10CDR-A-V1 Datasheet - Page 15

Micro Programmable Logic Controller

CPM1A-10CDR-A-V1

Manufacturer Part Number
CPM1A-10CDR-A-V1
Description
Micro Programmable Logic Controller
Manufacturer
Omron
Datasheets

Specifications of CPM1A-10CDR-A-V1

Output Type
Relay
External Width
66mm
Supply Voltage Max
240VAC
External Depth
70mm
Mounting Type
DIN Rail
External Height
90mm
Supply Voltage Min
100VAC
Approval Bodies
UL, CSA, CE
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Temperature Sensor Units
By mounting a Temperature Sensor Unit (CPM1A-TS001/TS002/TS101/TS102) to the PLC, input can be obtained from a thermocouple or platinum
resistance thermometer, and temperature measurements can be converted to binary data (4-digit hexadecimal) and cyclically updated in the input
area of the CPU Unit.
Specifications
Note: The indication accuracy when using a K-type thermocouple for temperatures less than –100°C is ±4°C ±1 digit max.
Input Temperature Ranges for CPM1A-TS001/002
The rotary switch can be used to make of the following range and input type settings for CPM1A-TS001/002 models.
Input Temperature Ranges for CPM1A-TS101/102
The rotary switch can be used to make of the following range and input type settings for CPM1A-TS101/102 models.
Specifications CPM1A-TS101-DA
DeviceNet I/O Link Unit - CPM1A-DRT21
By connecting the DeviceNet I/O Link Unit (CPM1A-DRT21), the CPM1A can function as the slave of a DeviceNet Master Unit.
In this configuration, 32 input- and 32 output bits are exchanged with the Master Unit.
Specifications
PROFIBUS-DP I/O Link Unit - CPM1A-PRT21
By connecting the PROFIBUS-DP I/O Link Unit (CPM1A-PRT21), the CPM1A can function as the slave of any PROFIBUS-DP Master Unit.
In this configuration, 16 input- and 16 output bits are exchanged with the Master unit.
Specifications
54
Item
Model
Number of inputs
Input types
Indication accuracy
Conversion time
Converted temperature data
Isolation method
Input type
K
J
Input type
Pt100
JPt100
Item
Model
Number of inputs
Input types
Temperature range
Converted temperature data
Indication accuracy
Number of outputs
Output type
Load resistance
Output resolution
Output accuracy
Conversion time
Isolation method
Item
Master/slave
Number of I/O points allocated to Master
Number of words allocated from CPM1A’s I/O memory
Node address setting method
Item
Master/slave
Number of I/O points allocated to Master
Number of words allocated from CPM1A’s I/O memory
Node address setting method
Specifications
CPM1A-TS001/002
2 (TS001), 4 (TS002)
Thermocouple K, J switchable
(Note: Same type for all input points.)
The larger of ±0.5% of the indicated value and ±2°C ±1 digit max. [The larger of 0.5%of the indicated value and 1°C]
250 ms/2 points (TS001, TS101); 250 ms/4 points (TS002, TS102)
Binary (4-digit hexadecimal)
Photocoupler isolation between the temperature input signals.
Range (°C)
–200 to 1300
0.0 to 500.0
–100 to 850
0.0 to 400.0
Range (°C)
–200.0 to 650.0
–200.0 to 650.0
Specifications
CPM1A-TS101-DA
2
Pt100
-40 to 250°C
16-bit, 2’s complement, 0.1°C resolution
1.0% of full scale max.
1
0 to 10 V, -10 to 10 V, 4 to 20 mA
2 k min. (voltage output), 500 max. (current output)
8 bit + sign (1/256, 1/512 for -10 to 10 V)
1.0% of full scale max.
60 ms (all channels)
Photocoupler isolation between I/O signals and PLC
Specification
DeviceNet Slave
Input: 32 points / Output: 32 points
Input: 2 words / Output: 2 words
(Allocated in the same way as other Expansion Units).
Set using DIP switch.
Specification
PROFIBUS-DP slave (OC_0658.GSD)
Input: 16 points / Output: 16 points (Intel/Motorola format selectable by DIP switch)
Input: 1 word / Output: 1 word
(Allocated in the same way as other Expansion Units).
0-99 using 2 rotary switches
CPM1A-TS101/102
2 (TS101), 4 (TS102)
Pt100, JPt100 switchable
(Note: Same type for all input points.)
Range (°F)
–300 to 2300
0.0 to 900.0
–100 to 1500
0.0 to 750.0
Range (°F)
–300 to 1200.0
–300 to 1200.0
1 digit max.
Programmable Controllers