CN41/D/RN C & S, CN41/D/RN Datasheet

SOUNDER, CARILLON, 24VDC, RED

CN41/D/RN

Manufacturer Part Number
CN41/D/RN
Description
SOUNDER, CARILLON, 24VDC, RED
Manufacturer
C & S
Series
Carillonr
Datasheet

Specifications of CN41/D/RN

Transducer Function
Sounder
Input Current
20mA
Tones
32 Tone
Sound Level Spl
104dB
Sound Level Distance
1m
Colour
Red
External Length / Height
110mm
Supply Voltage
2
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
DIMENSIONS (mm)
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
C l i f f o r d & S n e l l
All dimensions are approximate only and subject to change without notice as are technical features
resulting from continual development and improvement
CONFIGURATOR
Unit Type
Supply Voltage
Material
24Vdc
Red Normal
Carillon
100 (3.9”)
90 (3.5”)
80 (3.2”)
Electronic Sounder
KM91259
MOUNTING
MAIN FEATURES
BS EN 54-3 : 2001 incorporates amendment A1 : 2002
The Carillon alarm units should be mounted to a reasonably flat
wall or bulkhead of suitable material using the internal fixing holes
(mounting gasket supplied).
The recommended fixing screws are dia 4.5max x 20mm long.
To maintain the integrity of the weather seal, the cable must be fitted
using a suitable sealed gland.
LINE MONITORING (DC Only)
APPROVAL SPECIFICATION
TECHNICAL SPECIFICATION
- 3 Wire 2 stage or 2 wire single stage, monitor via reverse
- 2 Wire 2 stage i.e. bi-polar inputs, monitor via threshold
End of line resistor. Minimum 3K3 ohm 0.5 watts, wire-wound or metal
film type.
polarity
(applied voltage <1V)
monitored via reverse polarity
Versatile compact sounder
Low current consumption
High sound output
2 stage alarm by 2 wire bi-polar and 3 wire polarised control
Continuously rated
Complies with BS 5839
Easy installation
For 3 wire 2 stage alarm systems, line integrity maybe
32 selectable tones meeting international regulations
Sound selection via 5 way DIL switch
Red flame retardant ABS plastic enclosure
Operating temperature
Storage temperature
Operating voltage
Relative humidity
IP65 rated
Cable gland entry must be suitably sealed
Weight
Sound output
Volume control giving 18dB(A) adjustment
Minimum current consumption 20mA
Controlled document No. D7412-01-02 \\BGRICE\3 Issued\Data Sheets\CARILLON
104dB(A) @ 1 mtr
95% @ 40 deg C
–25 to +40 deg C
–40 to +70 deg C
24Vdc +/- 10%
0.25Kg
Web Site: www.cliffordandsnell.com
Email: cliffordandsnell@aol.com
Tom Cribb Road, Thamesmead,
Fax: +44 (0)20 8317 2400
Tel: +44 (0)20 8316 4477
or (0)20 8317 1717
London SE28 0BH

Related parts for CN41/D/RN