RM4TR32 SQUARE D, RM4TR32 Datasheet - Page 7

no-image

RM4TR32

Manufacturer Part Number
RM4TR32
Description
PHASE FAILURE RELAY 300V 5A RM4
Manufacturer
SQUARE D
Datasheet

Specifications of RM4TR32

Rohs Compliant
YES
Phase Type
3 Phase
Supply Voltage Max
300V
Supply Current Max
3A
Switching Voltage Max
250VAC
Relay Mounting
DIN Rail
Product data sheet
Technical Description
Function Diagram
Overvoltage and Undervoltage Detection
Functions "Fault detection delayed" or "Fault detection extended” (by switch selector)
t
U
S
15/18,
15/16;
25/28,
25/26
Relay status: black color = energized.
NOTE: In order to be detected, the duration of the overvoltage or undervoltage must be greater than the measuring cycle time (80 ms).
Time delay (adjustable from 0.1 s to 10 s with a selector switch)
3-phase supply voltage monitored (between terminals L1, L2 and L3)
Overvoltage or undervoltage setting
Output relays connections (refer to Connections and Schema)
RM4TR32
7