Technical Data
Electrical characteristics
Standards
The devices comply with: EN IEC 61058-1 and EN IEC 60947-5-1, EN
IEC 60947-5-5 (Emergency-stop)
Electrical life
≥50 000 cycles of operation at 250 VAC, 5 A, cosφ 0.95, as per EN IEC
60947-5-1
Switching Element of Emergency-stop 6050 cycles of operation, as per
EN IEC 60947-5-5
Electrostatic discharge
Keylock switch
Electric strength
4000 VAC, 50 Hz, 1 min., as per DIN IEC 60512-2
between all terminals and earth
Overvoltage category
III, as per EN IEC 60947-5-1
Protection class
Class II, as per EN IEC 61058-1
Degree of pollution
3, as per EN IEC 60947-1
Electrical characteristics for silver contacts
Rated Operational Voltage Ue
250 VAC/DC as per EN IEC 60947-1
Rated Insulation Voltage Ui
320 VAC, as per EN IEC 60947-5-1
Rated Impulse Withstand Voltage Uimp
4 kV, as per EN IEC 60947-5-1
Contact resistance
New state ≤50 mΩ, as per DIN IEC 60512-2-4, measured at 100 mA,
10 V
Conventional free air thermal current Ith
5 A, as per EN IEC 60947-5-1
the maximum current in continuous operation and at ambient
temperature must not exceed the quoted maximum values.
Switch rating
Switch rating AC with silver contact and srew terminal, service
category AC-15, as per EN IEC 60947-5-1
Voltage
Current
Switch rating with silver contact and screw terminal, service category
DC-13, as per EN IEC 60947-5-1
Voltage
Current
Recommended minimum operational data
20 VAC/DC, 100 mA
105
125 VAC
3 A
250 VDC
0.2 A
11 kV
250 VAC
2 A