RA2410-D06T CARLO GAVAZZI, RA2410-D06T Datasheet - Page 2

SSR, DIN RAIL MOUNT, 280VAC, 32VDC, 10A

RA2410-D06T

Manufacturer Part Number
RA2410-D06T
Description
SSR, DIN RAIL MOUNT, 280VAC, 32VDC, 10A
Manufacturer
CARLO GAVAZZI
Datasheet

Specifications of RA2410-D06T

Control Voltage Type
DC
Control Voltage Range
3VDC To 32VDC
Operating Voltage Range
24VAC To 280VAC
Peak Surge Current
90A
Load Current
10A
Switching Mode
Zero Cross
RA 24.. -D 06 T, RA 24.. -D 06 TF
Input Specifications
Control voltage range
Pick-up voltage
Drop-out voltage
Reverse voltage
Input impedance
Response time pick-up
Response time drop-out
Output Specifications
Rated operational current AC 1 10 Arms
Minimum operational current
Rep. overload current t=1 s
Non-rep. surge current t=20 ms 90 A
Off-state leakage current
@ rated voltage, frequency
I
Critical dI/dt
On-state voltage drop
@ rated current
Critical dV/dt commutating
Critical dV/dt off-state
Thermal Specifications
Operating temperature
Storage temperature
Junction temperature
Rth junction to case
Rth junction to ambient
2
Wiring Diagram
2
t for fusing t=1-10 ms
Control
input
RA 24 .. -D 06T/TF
3 to 32 VDC
1.5 k
RA 2410 -D 06 T/F
20 mArms
RA 2410 -D 06 T/TF
-40 to +100 C (-40 to +212ºF)
-40 to +100 C (-40 to +212ºF)
3 V
1 V
32 VDC
1/2 cycle
1/2 cycle
30 A
5 mArms
40 A
10 A/ s
1.6 Vrms
10 V/ s
250 V/ s
125 C (≤257ºF)
2.5 K/W
12.5 K/W
p
p
2
s
Line/load
Functional Diagram
RA 2425 -D 06 T/F
25 Arms
20 mArms
200 A
RA 2425 -D 06 T/TF
-40 to +100 C (-40 to +212ºF)
-40 to +100 C (-40 to +212ºF)
50 A
5 mArms
200 A
10 A/ s
1.6 Vrms
10 V/ s
250 V/ s
125 C (≤257ºF)
1.8 K/W
12.5 K/W
Control
input
p
p
2
s
Specifications are subject to change without notice
Mains input/load output
Load output/mains input

Related parts for RA2410-D06T