RJ1P23MBT50ECS CARLO GAVAZZI, RJ1P23MBT50ECS Datasheet

SSR, DIN RAIL MOUNT, 265VAC, 30VDC, 50A

RJ1P23MBT50ECS

Manufacturer Part Number
RJ1P23MBT50ECS
Description
SSR, DIN RAIL MOUNT, 265VAC, 30VDC, 50A
Manufacturer
CARLO GAVAZZI
Datasheet

Specifications of RJ1P23MBT50ECS

Control Voltage Type
AC
Control Voltage Range
19.2VDC To 30VDC
Operating Voltage Range
90VAC To 265VAC
Peak Surge Current
1.9kA
Load Current
50A
Switching Mode
Proportional Output
Specifications are subject to change without notice (30.03.2007)
Selection Guide
Rated operational
voltage
230VACrms
General Specifications
Operational voltage range
Blocking voltage
Power factor
Operational frequency range
Output indication
Alarm indication
Data indication
SSR fault detection
Over temperature protection
Output power
Thermal Specifications
Solid State Relays
SOLITRON MIDI Modbus Communication Interface
Type RJ1P MB
Product Description
The RJ1P MB series is a solid
state relay equipped with a
fieldbus communication inter-
face.
The relay operates under con-
trol of a microcontroller that
handles communication, moni-
tors operational parameters
and controls the SSR thyristor
firing. The RJ1P MB supports
Type Selection
Switching
mode
P: Proportional 23: 230VACrms
Operating temperature
Storage temperature
Output
Rated operational
voltage
Blocking voltage
650Vp
the Modbus RTU communica-
tion protocol, operating over an
RS485 interface.
The communication interface
allows modification and read-
ing of several parameters very
quickly through a single con-
nection.
tion is easily accessible for
troubleshooting and repair.
-30 to +70ºC (-22 to +158 ˚F)
-40 to +100ºC (-40 to +212 ˚F)
90 - 265 VAC
650 V
>0,9 @ 230VAC
45-65 Hz
Green LED (dual intensity)
Red LED
Orange LED, flashing
Yes
Yes
0 – 99.6%
Control
input
MBT: 2-wire Modbus RTU
p
Diagnostic informa-
RMS
Supply voltage
24VDC
• AC semiconductor contactor
• MODBUS RTU interface over RS485
• RJ45 sockets for easy installation
• Dual sockets for daisy chaining
• Multi-function – 4 selectable modes of operation:
• Operational ratings up to 50 AACrms and 230 VAC
• Temperature monitoring with over-temperature
• Opto isolation: > 4000 VACrms
• LED status indication
Output power resolution
Pollution degree
Installation category
Approvals
CE-marking
Ordering Key
Solid State Relay
Number of poles
Switching mode (Proportional)
Rated operational voltage
Control input type
Rated operational current
Terminal layout
Configuration options
Isolation
Rated isolation voltage
ON/OFF, Phase angle, Distributed full cycle, Burst firing
protection
Rated operational
current
50: 50AACrms
Input to output
Output to case
Mode 0 ON/ OFF
Mode 1 Phase angle
Mode 2 Full cycle
Mode 3 Burst firing
Control input
RS485 interface (2-wire)
RJ 1 P 23 MBT 50 E BC
Terminal
layout
E: Contactor
layout
1/1
1/256
1/256
1/32 – 1/256 depending
on time-base setting
2
III
UL, cUL
Yes
4000 VACrms
4000 VACrms
Rated operational
current (50 A)
RJ1P23MBT50EBC
RJ1P23MBT50ECS
RJ1P23MBT50ECV
Options
BC: Basic Controller
CS: Current Sensing
CV: Current & Voltage
Sensing
1

Related parts for RJ1P23MBT50ECS

RJ1P23MBT50ECS Summary of contents

Page 1

... Terminal Options layout E: Contactor BC: Basic Controller layout CS: Current Sensing CV: Current & Voltage Sensing Control input Rated operational current (50 A) RS485 interface (2-wire) RJ1P23MBT50EBC RJ1P23MBT50ECS RJ1P23MBT50ECV 1/1 1/256 1/256 1/32 – 1/256 depending on time-base setting 2 III UL, cUL Yes 4000 VACrms 4000 VACrms 1 ...

Page 2

RJ1P MB Housing Specifications Weight Approx. 415 g Housing material PBT Control terminal cable size AWG20) Min AWG12) or Max ...

Page 3

... Mode 2 Burst firing Mode 3 • Fault detection: Over temperature, SSR fault (shorted, 1/2 wave conduction, open circuit), Phase Loss, Full Load Loss Same features as RJ1P23MBT50EBC with additional: • Current monitoring Same features as RJ1P23MBT50ECS with additional: • Voltage monitoring • Power measurement 3 ...

Page 4

RJ1P MB LED indication The Green LED (Output The Yellow LED (Data) shows dual purpose indicator. When communication activity. 24V power is applied the Green lights up for the period of time LED is dimly lit. When the ...

Page 5

RJ1P MB Connection Examples RS485 from PLC/IPC Notes terminating resistor (value 100 to 130 2. 24V power may be applied through terminals 6A4, 4A2 or through the RJ-45 connector. If daisy chaining several devices using standard ethernet patch ...