120A.1-10SSTB AMPERITE, 120A.1-10SSTB Datasheet

TIME DELAY RELAY, SPST-NO, 10SEC, 120VAC

120A.1-10SSTB

Manufacturer Part Number
120A.1-10SSTB
Description
TIME DELAY RELAY, SPST-NO, 10SEC, 120VAC
Manufacturer
AMPERITE
Datasheets

Specifications of 120A.1-10SSTB

Contact Configuration
SPST-NO
Nom Input Voltage
120VAC
Delay Time Range
0.1s To 10s
Timing Adjustment
Resistor / Potentiometer
Relay Mounting
Panel
Timing Function
Delay-On-Release
Brand/series
STB Series
Contact Form
SPST-NO
Current, Rating
2 A
Function
Timing
Relay Type
Solid State
Repeatability
0.02
Standards
UL, CSA
Termination
Quick Connect
Timer Type
Off Delay
Timing Range
0.1 to 10 sec.
Voltage, Control
120 VAC
Timing Mode:
Power is applied to the relay prior to the timing cycle. Upon application of power to the
trigger input terminal the load is energized. When power is removed from the trigger
terminal the time delay cycle is initiated. At the end of the delay time the load is de-
energized. Reset is accomplished by reapplying power to the trigger input terminal.
Timing Diagram:
Contact Information:
Solid state switching device 1 form A; normally open series connection. Continuous
current rating 2 amperes. Maximum inrush 20 amperes. Voltage drop 2.5 volts RMS or
less @ 2 amperes. (For 10 ampere load current rating consult factory)
Delay-On-Release
STB Series
Solid State
Triggered
Timers
Solving your relay requirements since 1922
… 100% solid state circuitry - no
moving parts
… CMOS digital timing circuitry
… Fixed or field adjustable delays from
milliseconds to hours
… 2 amperes continuous load current
(10 amperes available, consult factory)
… UL File # Pending
… CSA File #Pending

Related parts for 120A.1-10SSTB

120A.1-10SSTB Summary of contents

Page 1

... Power is applied to the relay prior to the timing cycle. Upon application of power to the trigger input terminal the load is energized. When power is removed from the trigger terminal the time delay cycle is initiated. At the end of the delay time the load is de- energized. Reset is accomplished by reapplying power to the trigger input terminal. ...

Page 2

Solving your relay requirements since 1922 Timing Specifications: Timing: factory fixed seconds to 100 hours in any of the ranges below. Timing is set by user supplied resistor or potentiometer. Custom timing available. Timing ranges ...

Page 3

Solving your relay requirements since 1922 120V 105V 130V 230V 190V 255V External Resistor Selection: Wiring Diagram: Mechanical Information: Enclosure 3/4 inch black plastic, epoxy sealed. Center hole mounting. Four or six 1/4 inch quick connect ...

Page 4

... Solving your relay requirements since 1922 Definition of a part number for the Amperite STB Series Time Delay Relay: Example: A: Denotes nominal input voltage. Voltages available: 12V, 24V, 120V & 230V AC; 12V, 24V, 48V & 110V DC. Custom voltages are available. B: Denotes type of input power required for operation Alternating Current Direct Current. C & ...

Related keywords