H3YN-2-24DC Omron, H3YN-2-24DC Datasheet - Page 3

TIMER, MULTIFUNCTION, DPDT

H3YN-2-24DC

Manufacturer Part Number
H3YN-2-24DC
Description
TIMER, MULTIFUNCTION, DPDT
Manufacturer
Omron
Datasheet

Specifications of H3YN-2-24DC

Contact Configuration
DPCO
Nom Input Voltage
24VDC
Delay Time Range
0.1s To 10min
Adjustment Type
Knob
Relay Mounting
Plug-In
Svhc
No SVHC (15-Dec-2010)
Coil Voltage Vdc Nom
24V
Timing Adjustment
DIP Switch
H3YN
Note: Terminal screw sections are excluded.
Accuracy of operating time
Setting error
Reset time
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
Impulse withstand voltage
Noise immunity
Static immunity
Enclosure rating
Weight
EMC
Approved standards
Characteristics
Item
Min. power-opening time: 0.1 s max. (including halfway reset)
100 M min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed
non-current-carrying metal parts) (see note)
2,000 VAC, 50/60 Hz for 1 min (between operating power circuit and control output)
2,000 VAC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model)
1,500 VAC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Destruction: 10 to 55 Hz, 0.75-mm single amplitude
Malfunction: 10 to 55 Hz, 0.5-mm single amplitude
Destruction: 1,000 m/s
Malfunction: 100 m/s
Operating:
Storage:
Operating:
Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:
Between power terminals:
3 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1 kV for 12 VDC, 24 VDC, 48 VDC, 24 VAC
Between exposed non-current-carrying metal parts:
4.5 kV for 100 to 120 VAC, 200 to 230 VAC, 100 to 110 VDC, 125 VDC
1.5 kV for 12 VDC, 24 VDC, 48 VDC, 24 VAC
Destruction: 8 kV
Malfunction: 4 kV
IP40
Approx. 50 g
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance: ENV50141:
Immunity Burst:
UL508, CSA22.2 No. 14
Conforms to VDE0435/P2021, VDE0110 (for in-panel use)
Conforms to EN50081-2, EN50082-2
1% FS max. (1 s range: 1% 10 ms max.)
10% 50 ms FS max.
2% FS max.
2% FS max.
1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 s, 1-ns rise)
–10 C to 50 C (with no icing)
–25 C to 65 C (with no icing)
35% to 85%
DPDT:
500,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h)
4PDT:
200,000 operations min. (H3YN-4-Z/-41-Z: 100,000 operations min.)
(3 A at 250 VAC, resistive load at 1,800 operations/h)
2
(approx. 10G)
2
(approx. 100G)
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61000-4-2: 4 kV contact discharge (level 2)
ENV50140:
EN61000-4-4: 2 kV power-line (level 3)
H3YN-2/-21/-4/-41
8 kV air discharge (level 3)
10 V/m (amplitude modulated, 80 MHz to
1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
10 V (0.15 to 80 MHz) (level 3)
2 kV I/O signal-line (level 4)
H3YN
3