4300A-8-1 ARTISAN CONTROLS, 4300A-8-1 Datasheet - Page 2

SOLID STATE TIMER, 30SEC, 120VAC

4300A-8-1

Manufacturer Part Number
4300A-8-1
Description
SOLID STATE TIMER, 30SEC, 120VAC
Manufacturer
ARTISAN CONTROLS
Datasheets

Specifications of 4300A-8-1

Nom Input Voltage
120VAC
Delay Time Range
0.1s To 30s
Timing Adjustment
Resistor
Relay Mounting
Plug In
Supply Voltage
120VAC
Time Range Max
30s
Load Current Rms Max
1A
Time Range Min
0.1s
Brand/series
4300 Series
Current, Rating
10 mA-1 A
Function
Timing
Relay Type
Solid State
Repeatability
±1%
Standards
cULus, UL
Temperature, Operating, Maximum
85 °C
Temperature, Operating, Minimum
-20 °C
Termination
Quick Connect
Timer Type
Interval
Timing Range
0.1 to 30 sec.
Voltage, Control
120 VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Notice: Artisan Controls Corporation assumes no responsibility for customers applications or product design. The information and data contained herein is
the sole and exclusive property of Artisan Controls Corporation. Any duplication, misuse, or conversion of this information without the express written
consent of Artisan Controls Corporation is illegal and will result in damages including court costs and attorney fees being assessed against the party
misusing this property
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ordering Information Fixed Timing Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ordering Information Adjustable Timing Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Output Voltage Drop in "ON" State:
Fixed Timing Purchase Tolerance
Leakage Current in "OFF" State:
Repeatability Of Timing Period:
Example: 4300A-2-5 operates from 12V DC with adjustable timing from 30 to 8000 seconds.
4300F -
Example: 4300F-8-900-C operates from 115V AC with fixed timing of 900 seconds ± 10%.
4300A -
Part Number
Tel: 973-598-9400 • Fax: 973-598-9410 • Toll Free: 800-457-4950
Part Number
Artisan Controls Corporation, 111 Canfield Ave., Bldg B15-18, Randolph, NJ, 07869, USA
Data Sheet Revision Date:
Timing Range Tolerance:
Operating Temperature:
Agency Recognitions:
Transient Protection:
Voltage Tolerance:
Adjustable Timing:
Operating Voltage:
Operating Current:
V
Timing Variation:
Solid State Timers and Controllers
I S I T O U R W E B S I T E A T
Output Rating:
Recycle Time:
Timing Mode:
Fixed Timing:
Construction:
Dielectric:
Humidity:
Operating Voltage
Operating Voltage
-1
-2 (12V DC)
-3 (24V DC)
-4 (48V DC)
-5 (12V AC)
-6 (24V AC)
-7 (48V AC)
-8 (120V AC)
-9 (230V AC)
-1
-2 (12V DC)
-3 (24V DC)
-4 (48V DC)
-5 (12V AC)
-6 (24V AC)
-7 (48V AC)
-8 (115V AC)
-9 (230V AC)
(5V DC)
(5V DC)
12V DC, 24V DC, 48V DC, 12V AC 24V AC, 48V AC, 115V AC, 230V AC.
±20%, AC 50/60Hz.
All voltages < 20 mA plus load current requirements.
Interval.
From 0.1 seconds to 10,000 seconds.
2%, 5%, 10%, and 20%.
0.1 seconds to 8,000 seconds covered by 5 models.
Minimum time - 15% +0%, maximum time - 0% +15%.
±15% of set point over specified temperature and voltage range.
±1% nominal.
Operating voltage must be removed for a minimum of 200 milliseconds to
guarantee all timing and output circuits have reset.
Rated for 10mA to 1A inductive with inrush current to 25 A for 8 mS.
2V for DC models, 4V maximum for AC models.
1 mA maximum for DC models, 3 mA maximum for AC models.
Protected by silicon transient suppressors which respond to transients within 1
x 10
1500V rms all terminals to case.
-20°C to +85°C.
95% non-condensing.
Encapsulated module with .25 quick connect wiring terminals.
UL File E47858: Appliance Controls - Component ATNZ2 (US) & ANTZ8 (Can),
Auxiliary Devices - Component NKCR2 (US) & NKCR8 (Can).
April 7, 2009
-12
seconds to a peak pulse power dissipation of 1500 watts.
Timing remotely adjustable
Specify the fixed timing
period in seconds from
Timing In Seconds
Fixed Timing In Seconds
-1
-2
-3
-4 (10 - 4500)
-5 (30 - 8000)
by resistor across
timing terminals
0.1 to 10,000
(0.1 - 30 )
(2 - 1000)
: www.artisancontrols.com
(1 - 300)
the timing tolerance required only
Specify the dash number that
Fixed Timing Tolerance
on fixed timing units
-A 2%
-B 5%
-C 10 %
-D 20 %
represents

Related parts for 4300A-8-1