788-507 WAGO, 788-507 Datasheet

POWER RELAY, 1CO, 115VAC, 16A, DIN RAIL

788-507

Manufacturer Part Number
788-507
Description
POWER RELAY, 1CO, 115VAC, 16A, DIN RAIL
Manufacturer
WAGO
Datasheet

Specifications of 788-507

Relay Type
General Purpose
Coil Voltage Vac Nom
115V
Contact Current Max
16A
Contact Voltage Ac Nom
250V
Contact Configuration
SPDT
Coil Type
AC
Coil Current
8mA
Relay Mounting
DIN Rail
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Relay Socket with Small Switching Relay
Socket with relay (1 changeover contact) and status indication
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes
18.11.2009 / dj50700e.doc
Description
DC-Load limiting value graph
Note: Inductive loads have to be attenuated by
Socket with relay, AC 115 V, 1 changeover contact
300
200
100
Relay socket for DIN 35 carrier rails.
Status indication through pluggable LED module (red).
Insulated, pluggable jumper system suitable for both coil
and load side.
CAGE CLAMP
Solid wires, fine-stranded wires with crimped ferrules or
ultrasonically bonded wire ends can be inserted directly.
Quick exchange of the relay and the status indication
during maintenance, without having to detach the wiring.
Safe electrical isolation in accordance with DIN VDE 0140
Part 1.
50
40
30
20
10
0,1 0,2
an appropriate protective circuit in order to
protect relay coils and contacts !
0,5
®
1
S connection.
2
Similar photo
resistive load
5
Current (A)
10
Postfach 2880 • D-32385 Minden
Hansastr. 27 • D-32423 Minden
20
Technical Data
Contact material
Input nominal voltage U
Input voltage range
Current input at U
Max. switching voltage
Max. making current (resistive)
at 10 % continuous duty
Max. continuous current
Max. switching power
(resistive)
(resistive)
Max. number of switching
operations with/without load
Operating power
Pull-in/dropout/bounce time
Operation at normal rating
Dielectric strength
contact/coil
open contact
Nominal voltage acc. to
VDE 0110 Part1 / 4.97
IEC 60664-1
Mechanical life
Degree of protection
Relay type
Ambient operating temperature -25 °C ... +50 °C
Storage temperature
Dimensions (WxHxD)
Tel.:
Fax.:
05 71 / 8 87-0
05 71 / 8 87-169 Web:
N
(20 °C)
N
typ.
Item-No.
788-507
AgNi 90/10
AC 115 V
U
8 mA
AC 250 V
4 s (AC) 30 A
16 A
AC 4000 VA
DC see load limiting value graph
6 min
0.75 VA
7 ms / 3 ms / 3 ms
100 % continuous duty
5 kV
1 kV
250 V / 4 kV / 3
10 x 10
IP 20
RT 1
-40 °C ... +70 °C
(15x53*x86) mm / (0.59x2.09x3.39) in
* from upper edge of DIN 35 rail
E-Mail:
N
± 10 %
rms.
rms.
-1
/ 1200 min
6
switching operations
info@wago.com
http://www.wago.com
-1
Pack.-unit
pcs
D a t a s h e e t
1
1/2

Related parts for 788-507

788-507 Summary of contents

Page 1

... Dielectric strength contact/coil open contact Nominal voltage acc. to VDE 0110 Part1 / 4.97 IEC 60664-1 Mechanical life Degree of protection Relay type Ambient operating temperature -25 °C ... +50 °C Storage temperature Dimensions (WxHxD) 20 Item-No. 788-507 AgNi 90/10 AC 115 V N ± (20 ° 250 (AC 4000 VA DC see load limiting value graph ...

Page 2

... Standards / prescriptions DIN VDE 0140 Part1, DIN EN 61140 DIN VDE 0160, EN 50178 Class of protection II Approvals UL508 / CSA22.2 E175199 Only use replacement relay 788-174 for UL applications (see accessories) Accessories: Comb type jumper bar 18 A, 2-way 788-113 18 A, 3-way 788-114 18 A, 4-way 788-115 ...