3UG4633-1AL30 SIEMENS, 3UG4633-1AL30 Datasheet - Page 20

RELAY, DIGITAL MONITORING, VOLTAGE

3UG4633-1AL30

Manufacturer Part Number
3UG4633-1AL30
Description
RELAY, DIGITAL MONITORING, VOLTAGE
Manufacturer
SIEMENS
Series
3UGr
Datasheet

Specifications of 3UG4633-1AL30

Power Consumption
2W
Supply Voltage Max
275V
Relay Mounting
DIN Rail
Control Voltage Type
AC / DC
Contact Termination
Screw
External Depth
86mm
External Length / Height
110mm
External Width
22.5mm
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3UG Monitoring Relays for Electrical and Additional Measurements
Insulation monitoring
for ungrounded AC networks
Technical specifications
Dimensional drawings
Schematics
Connection diagram for networks up to 400 V AC
Operating range of the control supply voltage
Rated power
Frequency of the rated control supply voltage
• Response value
• Minimum internal resistance for AC
• Minimum internal resistance for DC
• DC measurement voltage
• Insulation voltage
• Reset/test function terminals (max. 10 m)
• Delay time in case of response
Output relay
Rated insulation voltage U
Overvoltage category
Degree of pollution
Impulse withstand voltage U
Degree of protection
Shock resistance
Vibration resistance
Permissible ambient temperature
• During operation
• During storage
Permissible mounting position
Conductor cross-section
Control circuit
Measuring circuit L/PE/ground
General data
PE
3 x 230/400 V AC
L1
L2
L3
N 230 V
N 115 V
A1-B2/A1-A2 for AC 115 V/230 V
A1-A2 for AC/DC 24...240 V
7/80
Monitoring Relays
A2 B2
A1
Siemens LV 1 T · 2007
1)
i
imp
1
) Only 3UG3081-1AK20.
A2 B2
A1
24 ... 240 V AC
110 ... 130 V AC
220 ... 240 V AC
Between supply, measurement,
and output circuit
According to IEC 664
According to IEC 664
According to VDE 0435, Part 303 kV
According to EN 60529
According to IEC 60068 Part 2-27 g/ms
According to IEC 60068-2-6
Solid
Finely stranded with end sleeve
1)
N 230 V
N 115 V
Test
Reset
L
PE Y2
11
14
12
Y1
R
© Siemens AG 2007
VA/W
VA
VA
Hz
k
k
k
V
V
s
V
Hz/mm 10-55/0.35
°C
°C
mm
mm
2
2
3UG30 81
-15 %... +10 %
8 / 2
3
3
50 ... 60
1...110
100
100
30 DC
415 AC
Y1-Y2
1
1 CO contact,
open-circuit principle
400 according to IEC 60947-1
III
3
4
IP50 enclosure, IP20 terminals
10
-25 ... 65
-40 ... 85
Any
2 x 0.75 ... 2.5
2 x 0.75 ... 2.5

Related parts for 3UG4633-1AL30