VAKPU MACROMATIC CONTROLS, VAKPU Datasheet - Page 2

VOLTAGE MONITORING RELAY, SPDT, 240VAC

VAKPU

Manufacturer Part Number
VAKPU
Description
VOLTAGE MONITORING RELAY, SPDT, 240VAC
Manufacturer
MACROMATIC CONTROLS
Series
VAKPUr
Datasheet

Specifications of VAKPU

Contact Configuration
SPDT
Power Consumption
3VA
Supply Voltage Max
240VAC
Relay Mounting
Plug In
Control Voltage Type
AC
Relay Terminals
8 Pin Octal
Control Voltage
240V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Operating Modes
These relays can be used as either overvoltage or undervoltage relays, depending on the output contact used:
Overvoltage Relay
Provides protection to equipment that cannot handle excess
voltages. Uses a normally closed contact (N.C.). As long as
the monitored voltage remains below the maximum voltage the
equipment can withstand (Pick-Up Setting), the relay remains
de-energized and the N.C. contact remains closed, keeping the
load energized. If the operating voltage increases beyond the
maximum rating of the equipment, the relay energizes and the
N.C. contact opens, turning off the load. When the voltage
falls below the Drop-Out Setting (hysteresis), the relay de-
energizes and the N.C. contact re-closes, turning on the load.
Application Data
Voltage Tolerance:
+50%/-40% of nominal voltage; AC voltages are 50-60Hz;
No supply (input) voltage is required.
Load (Burden): Less than 3VA
Voltage Settings:
Pick-up:
Drop-out: Adjustable from 80-95% of pick-up setting
Temperature:
-28
Output Contacts:
SPDT: 10A @ 240V AC/30V DC, 1/2HP @ 240V AC
Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations
Dimensions
1/09
o
to 65
o
Adjustable from 85-115% of nominal voltage
C (-20
o
to 150
o
F)
(60)
2.4
(43)
1.7
VOLTAGE MONITOR RELAYS
VAKPU Series Over/Undervoltage
Response Times:
Power Up:
Operate:
Release:
Indicator LED: Red steady when relay is energized; Green
steady when relay is off; and Green rapid flash when in power-
up mode.
Reset: As standard, reset is automatic upon correction of a
fault.
Approvals:
Undervoltage Relay
Provides protection to equipment that is required to
operate above a certain minimum voltage. Uses a
normally open contact (N.O.). As long as the monitored
voltage is above the minimum value required (Pick-Up
Setting), the relay will energize and the N.O. contact
closes, turning on the load. If the voltage drops below
the Drop-out Setting (the minimum voltage required
minus the hysteresis), the relay will de-energize and the
N.O. contact will re-open, turning off the load.
Low Voltage & EMC Directives
EN60947-1, EN60947-5-1
2 seconds fixed delay
0.1 - 10 seconds adjustable
0.1 - 10 seconds adjustable
File #E109466
(74)
2.9
(77)
Application Data & Dimensions
3.0
File #E109466
with
appropriate
socket
208-240V Plug-in
Inches (Millimeters)
All Dimensions in
35