VAKP024D MACROMATIC CONTROLS, VAKP024D Datasheet - Page 2

VOLTAGE MONITORING RELAY, DPDT, 24VDC

VAKP024D

Manufacturer Part Number
VAKP024D
Description
VOLTAGE MONITORING RELAY, DPDT, 24VDC
Manufacturer
MACROMATIC CONTROLS
Series
VAr
Datasheet

Specifications of VAKP024D

Contact Configuration
DPDT
Power Consumption
3VA
Supply Voltage Max
24VDC
Relay Mounting
Plug In
Control Voltage Type
DC
Relay Terminals
8 Pin Octal
Control Voltage
24V
No. Of Poles
2
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Operating Modes
These relays can be used as either overvoltage or undervoltage relays, depending on the output contact used:
Overvoltage Relay
Provides protection to equipment that cannot handle excess
voltages. Uses a normally closed contact (N.C.). As long as the
monitored voltage remains below the maximum voltage the
equipment can withstand (Pick-Up Setting), the relay remains de-
energized and the N.C. contact remains closed, keeping the load
energized. If the operating voltage increases beyond the maxi-
mum rating of the equipment, the relay energizes and the N.C.
contact opens, turning off the load. When the voltage falls below
the Drop-Out Setting (hysteresis), the relay de-energizes and the
N.C. contact re-closes, turning on the load.
Application Data
Voltage Tolerance:
+25%/-50% of nominal voltage; AC voltages are 50-60Hz;
No separate supply (input) voltage is required.
Load (Burden): Less than 3VA
Voltage Settings:
Pick-up:
Drop-out: Adjustable from 75-95% of pick-up setting
Temperature:
-28
Output Contacts:
10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.),
1/3HP @ 120/240V AC (N.C.)
Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations
Dimensions
1/09
o
to 55
2.4 (60)
o
Adjustable from 85-115% of nominal voltage
C (-20
o
to 131
o
F)
1.7 (43)
VOLTAGE MONITOR RELAYS
Inches (Millimeters)
All Dimensions in
Response Times:
Operate: 500ms
Release: Adjustable 0.5 - 10 Seconds
Indicator LED: Red Steady when Relay is energized; Green
when Relay is Off.
Transient Protection:
10,000 volts for 20 microseconds
Reset: Automatic. Contact Macromatic for information on
units with Manual Reset.
Approvals:
VA Series Over/Undervoltage
2.9 (74)
Undervoltage Relay
Provides protection to equipment that is required to
operate above a certain minimum voltage. Uses a
normally open contact (N.O.). As long as the monitored
voltage is above the minimum value required (Pick-Up
Setting), the relay will energize and the N.O. contact
closes, turning on the load. If the voltage drops below
the Drop-out Setting (the minimum voltage required
minus the hysteresis), the relay will de-energize and the
N.O. contact will re-open, turning off the load.
Adjustable Time Delay on Drop-Out
Low Voltage & EMC Directives
3.5 (89)
EN60947-1, EN60947-5-1
File #E109466
Application Data & Dimensions
File #E109466
with
appropriate
socket
12-120V Plug-in
VAKP Only
31