PMDU MACROMATIC CONTROLS, PMDU Datasheet - Page 2

PHASE MONITORING RELAY SPDT/SPNC, 480VAC

PMDU

Manufacturer Part Number
PMDU
Description
PHASE MONITORING RELAY SPDT/SPNC, 480VAC
Manufacturer
MACROMATIC CONTROLS
Datasheet

Specifications of PMDU

Contact Configuration
SPDT / SPST-NC
Phase Type
3 Phase
Power Consumption
3VA
Supply Voltage Max
480VAC
Switching Voltage Max
240VAC
Operating Time Range
1s To 300s
Relay Mounting
SMD
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Application Data
Phase Loss:
Unit trips on loss of any Phase A, B or C.
Phase Reversal:
Unit trips if rotation (sequence) of the three phases is anything
other than A-B-C.
Undervoltage:
Adjustable from 80-95% of nominal voltage. Unit trips when
the average of all three lines is less than the adjusted set point
for a period longer than the adjustable time delay drop-out.
Overvoltage:
Fixed at 110% of nominal voltage. Unit trips when the average
of all three lines is greater than the fixed set point for a period
longer than the time delay drop-out.
Phase Unbalance:
Adjustable from 2 - 10% unbalance. Unit trips when any one of
the three lines deviates from the average of all three lines by
more than the adjusted set point . There is also a “Disable”
setting adjustment that will turn off the Phase Unbalance
Protection if nuisance tripping is a problem.
Output Contacts:
10A SPDT & SPNC @ 240V AC/30VDC,
1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.)
Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations
Response Times:
Power Up & Restart After Fault:
Drop-out Due to Fault:
Dimensions
1/09
Phase Loss & Reversal 100ms fixed
Phase Unbalance
Undervoltage
Overvoltage
(70)
2.7
(60)
2.4
1 - 300 seconds adjustable
2 seconds fixed
0.1 - 20 seconds adjustable
Fixed Time Based on Inverse
Time Curve
1.4 (35)
1.8 (45)
PHASE MONITOR RELAYS
Unbalance, and Under/Over Voltage
TWO 0.2 (5) MOUNTING HOLES
Phase Loss, Phase Reversal, Phase
Hysteresis: 2 - 3%
Load (burden): Less than 3VA
Temperature: -28
Mounting:
Does not require a socket. Can either be mounted directly on
35mm DIN track with no additional parts or to a back-panel
with two screws.
Indicator LED:
Reset:
As standard, reset is automatic upon correction of fault.
When a momentary-contact N.C. switch is wired across the
Manual Reset terminals (5 & 6), the unit switches to manual
reset mode and remote manual reset is available.
Approvals:
4.3 (110)
4.4 (112)
* Applies to 208-480V units only.
Green Steady
Green Flashing
Red Steady
Red Flashing
Amber Steady
Amber Flashing
Green / Red Alternating
Red / Amber Alternating
PMD Series Surface-Mount
LED Status
File #E109466
Application Data & Dimensions
o
to 65
o
C (-20
*
Nominal Voltage Set Error
Normal / Relay ON
Power Up / Restart Delay
Unbalance
Undervoltage / Overvoltage
Reversal
Loss
Undervoltage / Overvoltage
Trip Pending
o
to 150
Low Voltage & EMC Directives
EN60947-1, EN60947-5-1
o
Indicator
Inches (Millimeters)
F)
All Dimensions in
17