LC1K06105B7 SQUARE D, LC1K06105B7 Datasheet - Page 2

CONTACTOR, 3PST-NO, 24VAC, 15A, DIN RAIL

LC1K06105B7

Manufacturer Part Number
LC1K06105B7
Description
CONTACTOR, 3PST-NO, 24VAC, 15A, DIN RAIL
Manufacturer
SQUARE D
Datasheet

Specifications of LC1K06105B7

No. Of Poles
1
Contact Configuration
3PST-NO
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
24V
Relay Terminals
Screw
Nom Operating Power
3kW
Contact Voltage Ac Nom
690V
Operating Voltage
600VAC
Switching Power Ac1
1.5hp
Switching Power Ac3
3hp
Switching Current Ac1
20A
Switching Current Ac3
6A
Load Current Inductive
6A
Load Current Resistive
20A
Rohs Compliant
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Complementary
Environment
Control circuit voltage limits
Inrush power in VA
Hold-in power consumption in VA
Heat dissipation
Auxiliary contacts type
Signalling circuit frequency
Minimum switching current
Minimum switching voltage
Non overlap distance
Insulation resistance
IP degree of protection
Protective treatment
Ambient air temperature for operation
Ambient air temperature for storage
Operating altitude
Flame retardance
Mechanical robustness
Height
Width
Depth
Product weight
2
[Ui] rated insulation
voltage
Electrical durability
Mounting support
Standards
Product certifications
Connections - terminals
Operating time
Safety reliability level
Mechanical durability
Operating rate
0.2...0.75 Uc at <= 50 °C drop-out
0.8...1.15 Uc at <= 50 °C operational
30 VA at 20 °C
4.5 VA at 20 °C
1.3 W
Type instantaneous (1 NO)
<= 400 Hz
5 mA for signalling circuit
17 V for signalling circuit
0.5 mm
> 10 MOhm for signalling circuit
IP2x conforming to VDE 0106
TC conforming to DIN 50016
TC conforming to IEC 60068
-25...50 °C
-50...80 °C
2000 m without derating in temperature
Requirement 2 conforming to NF F 16-102
Requirement 2 conforming to NF F 16-101
V1 conforming to UL 94
Vibrations contactor opened 2 Gn, 5...300 Hz IEC 60068-2-6
Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6
Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Y axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on X axis 6 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Y axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on X axis 10 Gn for 11 ms IEC 60068-2-27
58 mm
45 mm
57 mm
0.18 kg
600 V for signalling circuit conforming to UL 508
690 V for signalling circuit conforming to IEC
60947-5-1
690 V for signalling circuit conforming to IEC
60947-4-1
690 V for power circuit conforming to IEC 60947-4-1
600 V for signalling circuit conforming to CSA 22-2
No 14
600 V for power circuit conforming to CSA 22-2 No
14
600 V for power circuit conforming to UL 508
1.3 Mcycles 6 A AC-3 at Ue <= 440 V
Printed circuit boards
BS 5424
IEC 60947
NF C 63-110
VDE 0660
CSA
UL
Solder pins 1.5 x 0.9 mm
10...20 ms coil energisation and NO closing
10...20 ms coil de-energisation and NO opening
B10d = 20000000 cycles contactor with mechanical
load conforming to EN/ISO 13849-1
B10d = 1369863 cycles contactor with nominal load
conforming to EN/ISO 13849-1
10 Mcycles
3600 cyc/h

Related parts for LC1K06105B7