Definite Purpose Contactor

C25BNF230B

Manufacturer Part Number
C25BNF230B
Description
Definite Purpose Contactor
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of C25BNF230B

Load Current Inductive
30A
Load Current Resistive
40A
No. Of Poles
2
Contact Configuration
DPST-NO
Relay Mounting
Panel
Coil Voltage Vac Nom
240V
Contact Voltage Ac Nom
600V
Horsepower
5hp
October 2008
Contents
Description
Compact 1- and 2-Pole
Product Description
Cutler-Hammer
double-pole, Type C25 contactors from
Eaton’s electrical business feature a
compact, efficient design with a low
VA coil and straight-through wiring.
New contactor housing design effec-
tively limits dust and other contami-
nants from magnet structure —
reduces or eliminates noise. These
economically priced, UL recognized/
CSA certified, ampere rated devices
are well suited for use in heating/air
conditioning, refrigeration, data pro-
cessing and food service applications.
CA08102001E
Contactors 20 – 40A
Product Description . . . . . . 35-3
Standards and
Technical Data —
Options . . . . . . . . . . . . . . . . 35-3
Dimensions. . . . . . . . . . . . . 35-4
Product Selection . . . . . . . . 35-4
Certifications . . . . . . . . . . 35-3
Specifications . . . . . . . . . 35-3
Compact 2-Pole
®
20 – 40A, single- and
Page
Standards and Certifications
Technical Data — Specifications
For more information visit: www.eaton.com
UL Recognized Components: UL File
Number E1491, Guides NLDX2 and
NLDX8
CSA Certified Components: CSA
C22.2 No. 14-05, File Number
238083 Class 3211 84
IEC 60947-4-1
EN 60947-4-1
Insulation Voltage: 690V
Current Rated and hp/kW Rated
Contacts: Double Break
Magnet Coil: Class F, 155°C
Contact Arc Covers are standard on
all Contactors
Standard Power Terminals —
Contactors are marked with Line
and Load Terminal Designations
Operating Temperature Range:
-13 to 158°F (-25 to 70°C)
Terminal Wire Range —
Mounting Position: Vertical,
Horizontal or Tabletop
Definite Purpose Contactors & Starters
Contactors
20 – 40A, Compact 1- and 2-Pole — C25
5/16" Hex Washer Head Screws
Quad (4) Quick Connect Terminals
on all Line and Load Terminals
Box Lugs available as option
Hex Washer Head Screws:
16 – 10 AWG, 30 lb-in torque
rating
Box Lugs: 16 – 10 AWG, 35 lb-in
torque rating; 8 AWG, 40 lb-in
torque rating; 6 – 4 AWG, 45 lb-in
torque rating
Table 35-2. Coil Characteristics
One-Pole
Two-Pole
Options
Table 35-3. Compact Options —
Factory Installed
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD-5C
AC Coil
Voltage
50/60 Hz
120
208/240
277
120
208/240
277
480
Description
Box lugs with quick connects for
20 – 40A contactors:
To order replace letter in the 6th posi-
tion of Catalog Number with letter F.
EXAMPLE: C25BNF240A
24
24
ARI 780/790 Standard
RoHS Compliance
1-Pole
1-Pole with shunt
2-Pole
Max.
Inrush
VA
33
33
33
33
41
41
41
41
41
Max.
Sealed
VA
6
6
6
6
6.5
6.5
6.5
6.5
6.5
Max.
Sealed
Watts
2
2
2
2
3
3
3
3
3
Adder
U.S. $
35-3