XTPAXLSAD EATON CUTLER HAMMER, XTPAXLSAD Datasheet - Page 158

Line-Side Adapter

XTPAXLSAD

Manufacturer Part Number
XTPAXLSAD
Description
Line-Side Adapter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTPAXLSAD

For Use With
Eaton Cutler-Hammer XT Series Frame D Manual Motor Protectors
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
34-158
34
Standards and Certifications
UL 508 Type F Combination Motor
Controller
Note: For Type 2 Coordination of MMCs,
see Tables 34-249 through 34-251 on Pages
34-210 and 34-211.
Protection in Different Controller
Types
A UL 508 Type E Self-protected Manual
Combination Starter/Motor Controller
consists of a single device having inte-
gral short circuit protection, a main set
of contacts, motor overload protec-
tion, and may also include a UL listed
Line Side Adapter (see Table 34-187).
This type of controller is a legitimate
short circuit protective device and dis-
connect means for the downstream
motor. It does require an upstream
feeder short circuit protective device,
but does not require a dedicated
branch circuit protection or a discon-
nect means if used with a Line Side
Adapter. A UL 508 Type E rating means
that the unit clears a fault and does not
experience any welding of the power
poles. A UL 508 Type E self-protected
manual motor controller will remain
fully functional should a short circuit
within its ratings occur. E.g. XTPR.
An
Combination Motor Controller consists
of a UL Listed Type E Self-protected
Manual Combination Starter/Motor
Controller, a UL Listed Contactor, and
a UL Listed Line Side Adapter (see
Table 34-187). While the UL 508 Type E
self-protected manual motor protector
of this combination motor controller
device is a legitimate short circuit
protective device and disconnect
means for the downstream motor,
the contactor is not “self-protected.”
E.g. XTFC, XTFR.
In addition, as a complete assembly or
modular components, the device
should have Type 2 Coordination certi-
fication. Type 2 Coordination means
the Starter or the Controller must
exhibit little or no damage following a
major short circuit fault and should be
able to be returned to proper service
without replacing any parts.
IEC Type 2 Approved per
IEC 60947-4-1
UL Listed File No. E245398
CE Mark
IEC Contactors & Starters
XT IEC Power Control
Combination Motor Controllers
UL 508 Type F Self-protected
Table 34-187. MMC and CMC Applications
Reference: Technical Paper AP03402001E.
Note: Line Side Adapters are not required for non-U.S. applications. Most countries outside
of the U.S. classify the MMP as a thermal magnetic circuit breaker.
For more information visit: www.eaton.com
SCPD = Short Circuit Protective Device (Circuit Breaker, Fuses).
MMC = Manual Motor Controller
XTSC / XTSR
Using the in-panel Main
SCPD
without a factory
assembled LSA.
Not required
Manual Motor Controller
Line Side Adapter (LSA)
Group Installation
XT IEC Manual & Combination Motor Controllers
and an MMC
Only Upstream Feeder SCPD
assembled LSA; no dedicated in-panel Main SCPD
for CMC.
UL 508 Type F Combination Motor Controller
XTFC / XTFR
Combination Motor Controller
Required — Factory
Assembled
Line Side Adapter (LSA)
required with factory
CA08102001E
March 2009