30C30-1023-155-5120 DURAKOOL, 30C30-1023-155-5120 Datasheet

CONTACTOR, 3PST-NO, 120VAC, 40A, PANEL

30C30-1023-155-5120

Manufacturer Part Number
30C30-1023-155-5120
Description
CONTACTOR, 3PST-NO, 120VAC, 40A, PANEL
Manufacturer
DURAKOOL
Datasheet

Specifications of 30C30-1023-155-5120

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
Panel
Coil Voltage Vac Nom
120V
Relay Terminals
Screw/Quick Connect
Nom Operating Power
7.5VA
Contact Voltage Ac Nom
600V
Operating Voltage
600VAC
Switching Power Ac1
5hp
Switching Power Ac3
20hp
Switching Current Ac1
40A
Switching Current Ac3
30A
Load Current Inductive
30A
Load Current Resistive
40A
3 0 C
definite purpose contactors
30C
Ordering Codes
Contact Ratings
Contact material
Contact number & arrangement
Termination Codes (see drawings for full specifications)
Reserved for Customer Specific Requirements
Page 1 of 8
American Electronic Components Inc., 1101 Lafayette St., Elkhart, IN 46516
Toll Free: (888) 847-6552, Tel: (574)-295-6330
Cover protection category
20 - 20 FLA
25 - 25 FLA
30
40
50
60
75
90
120
150
10 - AgCdO (standard)
70 - AgSnOInO (special)
1
2
3
4
5
6
7
21
22
23
24
43
1 - no overall cover, IP00
000 to 999 - optional customer specific number
- # 10-32 combination phillips screw with quad QC blades (20-30FLA)
- Same as 1 with sems screw and pressure plate
- #14-4 box lug with quad QC blades (box lug with quick connect)
- #14-4 box lug with dual QC blades (box lug with quick connect) standard
- #10-32 combination phillips screw with dual QC blades (20-30FLA)
- #14-2 box lug with QC blades
- #14-1 box lug with QC blades
- 30 FLA
- 40 FLA
- 50 FLA
- 60 FLA
- 75 FLA
- 90 FLA
- SPST-NO
- DPST-NO
- 3PST-NO
- 4PST-NO
- 3P (DPST-NO + SPST-NO)
- 120 FLA
- 150 FLA
Type
Contact
material
Contact number
& arrangement
Cover protection
category
www.aecsensors.com
Terminals
Terminations
T
Terminals
L
30C
Definite Purpose Contactor
20FLA - 150FLA
Robust 1-4Pole Contactor
Industry Standard Mounting
Arc Covers as standard
UL File No: E61703
RoHS Compliant
see Tables 2, 4, 6
Coil code
Additional
features

Related parts for 30C30-1023-155-5120

30C30-1023-155-5120 Summary of contents

Page 1

... Ordering Codes Type Contact Ratings FLA FLA FLA FLA FLA FLA FLA FLA 120 - 120 FLA 150 - 150 FLA Contact material 10 - AgCdO (standard AgSnOInO (special) Contact number & arrangement 21 - SPST- DPST- 3PST- 4PST- (DPST-NO + SPST-NO) Cover protection category ...

Page 2

... AgCdO, AgSnO Model No Full Load Amps (FLA) 30C20-1021 20 30C20-1022 20 30C25-1021 25 30C25-1022 25 30C30-1021 30 30C30-1022 30 30C40-1021 40 30C40-1022 40 Coil Data Voltage: 24-277VAC, 50/60Hz. See coil data below. (480VAC available but not UL approved) Insulation Class: UL Class B (130°C) Coil Code Rated Voltage Coil Resistance 50/60Hz ...

Page 3

... Pole General Specifications INITIAL DIELECTRIC STRENGTH Between Contacts & Coils: 2,200 VAC Between Poles: 2,200 VAC (includes shunt) Between Open Contacts: 2,200 VAC (no shunt) ARC COVER Standard INSULATION SYSTEM O 130 C Class B TEMPERATURE RANGE - + +150 F) UNIT WEIGHT 1 Pole 0 ...

Page 4

... Model No. Full Load Amps Poles FLA 30C20-1023 20 30C25-1023 25 30C25-1024 30C30-1023 30 30C30-1024 30C40-1023 40 30C40-1024 Coil Data Voltage: 24-277VAC, 50/60Hz. See coil data below. (480VAC available but not UL approved) Insulation Class: UL Class B (130°C) 3 Pole Coil Code Rated Voltage Coil Resistance 50/60Hz Ohms ...

Page 5

... Pole General Specifications INITIAL DIELECTRIC STRENGTH Between Contacts & Coils: 2,200 VAC Between Poles: 2,200 VAC Between Open Contacts: 2,200 VAC ARC COVER Standard on 40 FLA INSULATION SYSTEM O 130 C Class B TEMPERATURE RANGE - + +150 F) UNIT WEIGHT ...

Page 6

... Pole Contact Data Arrangements: 3 Form X (3PST-NO-DM) 4 Form X (4PST-NO-DM) Material: AgCdO, AgSnOInO Contact Ratings: Model No. Full Load Amps FLA 30C50-1023 50 30C60-1023 50 30C75-1023 50 30C90-1023 50 Coil Data Voltage: 24-277VAC, 50/60Hz. See coil data below. (480VAC available but not UL approved) Insulation Class: UL Class B (130°C) ...

Page 7

... Pole General Specifications INITIAL DIELECTRIC STRENGTH Between Contacts & Coils: 2,200 VAC Between Poles: 2,200 VAC Between Open Contacts: 2,200 VAC ARC COVER Standard INSULATION SYSTEM O 130 C Class B TEMPERATURE RANGE - + +150 F) UNIT WEIGHT 50-60FLA 2 lb 75-90FLA ...

Page 8

... Box Lug 14-4 AWG Cu/Al 75-90FLA Box Lug 14-1 AWG Cu/Al Auxillary Switches for 3 & 4 Pole contactors (20-40FLA) Description Single unit interlock configuration. One on each side - max set up two switches Single unit interlock configuration. ...