173364 Weidmuller, 173364 Datasheet - Page 41

CROSS CONNECT, 30WAY

173364

Manufacturer Part Number
173364
Description
CROSS CONNECT, 30WAY
Manufacturer
Weidmuller
Series
ZQVr
Datasheet

Specifications of 173364

Accessory Type
Jumper
No. Of Positions
30
Svhc
No SVHC (15-Dec-2010)
Connector Type
Jumper (Busbar)
No. Of Ways
30
Pitch Spacing
8.1mm
For Use With
ZQV6/30 Terminals
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Three-phase Current Transformer
Circuit with 12 WTL 6/3/STB
Requirement
1. The K-point must be routed together
2. 3 ammeters or relays (network protec-
3. The current flowing via the K-point must
4. It must be possible to disconnect the
5. It must be possible to »daisychain« con-
Solution
With 12 WTL 6/3/STB disconnect test ter-
minal blocks, a three-phase current trans-
former circuit can be realised with 3
ammeters that are connected in series.
L1 Residual Current Measurement
Ammeter hard-wired =>
Cross-connection slider opened
Control ammeter connected =>
Slide linck opened
L2 Transformer Short-Circuit
Cross-connection slider closed =>
Ammeter disconnected
L-3 Control Measurement by External
Ammeter
Control ammeter connected =>
Slide linck opened
3 cross-connection sliders closed =>
3 ammeter disconnected
Three-phase
Current Transformer Circuit
with WTL 6/3/STB
from the transformers to the measure-
ment terminal set, so that only 4 wires
are required.
tion) must be switchable in series for
each phase
be able to be measured with control
measurement devices during operation.
ammeters individually, without operating
the transformer open-circuit. All remai-
ning measurement devices must remain
in operation without any change.
trol measurement devices and transdu-
cing sensors for each phase; these
devices may be connected with the help
of test plugs.
2/29
2