2866514 Phoenix Contact, 2866514 Datasheet - Page 10

no-image

2866514

Manufacturer Part Number
2866514
Description
DIODE REDUNDANCY MODULE 24VDC
Manufacturer
Phoenix Contact
Series
Trior
Datasheet

Specifications of 2866514

Accessory Type
Redundancy Module
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With/related Products
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
104278_en_00
30
20
12
0
-25
TRIO-DIODE
TRIO-DIODE 2
TRIO-DIODE 1
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
20
30
40
50
60 70
max. 60 V, 100 mA
max. 60 V, 100 mA
T [°C]
www.phoenixcontact.com
Signaling
A floating relay contact and "Redundancy OK" LED are
available for monitoring redundancy. In normal operation
where input voltage > 8 V DC at input terminals "IN1+" and
"IN2+", the relay contact (13/14) is closed and the
"Redundancy OK" LED lights up.
If the input voltage falls to below the value of 8 V DC at one of
the input terminals, the floating relay contact opens and the
"Redundancy OK" LED goes out.
Floating, current-limited "Redundancy OK" signal contacts
are to be connected in series for monitoring redundancy. If
monitoring the redundancy is not necessary, the "GND
signal" does not need to be connected.
Thermal behavior
The device can be operated at an ambient temperature of -25
°C to +70 °C. For ambient temperatures above +55 , the
output current must be reduced by 2.5% per Kelvin increase
in temperature.
TRIO-DIODE/12-24DC/2X10/1X20