MIT510/2 Megger, MIT510/2 Datasheet

Insulation Testers / Megohmmeters A/D 5KV MEGGER

MIT510/2

Manufacturer Part Number
MIT510/2
Description
Insulation Testers / Megohmmeters A/D 5KV MEGGER
Manufacturer
Megger
Datasheet

Specifications of MIT510/2

Lead Free Status / RoHS Status
Lead free / RoHS Compliant
MIT510/2, MIT520/2 and MIT1020/2
5-kV and 10-kV Insulation Resistance Testers
DESCRIPTION
The new MIT510/2 and 520/2, 5-kV and MIT1020/2, 10-kV
insulation resistance testers are all designed specifically to
assist the user with the testing and maintenance of high
voltage equipment. The instruments are designed in a
landscape style which is more familiar and user friendly.
The MIT510/2 and MIT520/2 measures to 15 TΩ, replacing
the ambiguous “infinity” reading with an actual number
that can be used for predictive/preventive trending on the
highest quality insulation. Both units are supplied with test
leads with medium insulated clips.
The MIT510/2 has the facility to set the test voltage in
steps from 250 V to 5000 V and the MIT520/2 has the
ability to set the test voltage from 50 V to the maximum
output voltage.
The MIT1020/2 offers a measurement range to 35 TΩ in
order to provide trending values for the best of insulating
materials used on the higher capitalized equipment. The
model features an expanded test voltage range from 50 V
to 10 kV, in 10 V increments to 1 kV and 25 V increments
above. The MIT1020/2 is supplied with two sets of test
leads, one with medium insulated clips and the other with
large insulated clips.
All three instruments have a large, easy-to-read backlit LCD
making them equally suitable for use in both bright
sunlight and poorly lit environments. Information displayed
includes resistance, voltage, leakage current, capacitance,
battery status and time constant. In addition, the elapsed
time is displayed constantly, removing the need for
separate timers. The MIT520/2 and MIT1020/2 allow up to
3 timed measurement positions to be set, which simplifies
DAR testing.
A built-in integral timer starts automatically at the
beginning of a test, and displays in minutes and seconds.
At the end of any test, capacitive loads are automatically
discharged and the decaying voltage displayed. The timer
enables the performance of an automatic IR test with the
MIT510/2, while the MIT520/2 and MIT1020/2 add the
capability of preprogrammed DAR, PI, SV and DD. The
MIT520/2 and MIT1020/2 include a selectable breakdown
or burn mode and an alarm mode, which allows the
operator to preset a specific resistance level. The unit will
beep until the limit is exceeded. The controls of the
instruments are clear and unambiguous, and a “quick start”
guide is included in the lid, eliminating the need to carry
manuals to site locations.
Redundant safety features make the instruments fully
amenable to safe operation in the more demanding high
voltage environment. The CAT IV 600 V safety rating
means that the instruments are protected for use on
outside applications and are protected against impulses to
8 kV.
for arc-flash protection. If the instrument is accidentally
connected to a live test item, external voltage will be
automatically displayed and testing inhibited above 50 V
(80 V on MIT1020/2). At the conclusion of a test,
dangerous static voltage on the test item is automatically
discharged and monitored on the display. All three models
are fitted with a guard terminal to enhance accuracy. The
guard test lead is included as standard with each
instrument.
Line supply or battery operated
Digital/analog backlit display
Measurement range to 15 TΩ (MIT510/2
and MIT520/2) and 35 TΩ (MIT1020/2)
CAT IV 600 V safety rating
Automatic dielectric absorption ratio,
polarization index, step voltage, and
dielectric discharge tests (MIT520/2 and
MIT1020/2)
RS232 or USB download of results
(MIT520/2 and MIT1020/2)
Ingress protection to IP65
3 mA short circuit current
5-kV and 10-kV Insulation Resistance Testers
Instrument design is in conformance with EN61010
MIT510/2, MIT520/2 and MIT1020/2

MIT510/2 Summary of contents

Page 1

... Both units are supplied with test leads with medium insulated clips. The MIT510/2 has the facility to set the test voltage in steps from 250 V to 5000 V and the MIT520/2 has the ability to set the test voltage from the maximum output voltage. The MIT1020/2 offers a measurement range to 35 TΩ ...

Page 2

... Diagnostic testing to isolate faulty components for repair. The MIT1020/2 in use at an industrial complex substation MIT510/2, MIT520/2 and MIT1020/2 5-kV and 10-kV Insulation Resistance Testers With its higher voltage testing capability, the MIT1020/2 is the perfect every day work tool for manufacturers, users and maintainers of rotating machinery ...

Page 3

... Alarm limit mode (MIT520/2 and MIT1020/2 only) allows for faster testing and less ambiguous result interpretation. SPECIFICATIONS Test Voltage MIT510/2: 250 V, 500 V, 1000 V, 2500 V, 5000 V MIT520/ steps steps MIT1020/ steps steps Insulation Resistance Range Digital display: MIT510/2 and MIT520/2: 10 kΩ TΩ ...

Page 4

... Easier operation Use a “Quick Start” guide conveniently located in the lid, always there for easy reference. MIT510/2, MIT520/2 and MIT1020/2 5-kV and 10-kV Insulation Resistance Testers Line or battery operation The operating flexibility you need when site conditions are unknown or long term testing is required ...

Page 5

... Following is a brief summary of the highlights of IEEE Standard 43-2000: Test voltages are recommended for windings rated greater than 12 kV. Both the insulation resistance and the polarization index test are recommended. MIT510/2, MIT520/2 and MIT1020/2 5-kV and 10-kV Insulation Resistance Testers MIT510/2 MIT520/2 15 TΩ 15 TΩ ...

Page 6

... Polarization index (PI) 8. Time constant 6 through 8 — Displays the ratio value or the resistance measured at the indicated time. Item [Qty] MIT510/2 5-kV Insulation Resistance Tester MIT520/2 5-kV Insulation Resistance Tester MIT1020/2 10-kV Insulation Resistance Tester Included Accessories lead set, medium insulated clips [3] ...