UPS - Uninterruptible Power Supplies 4)5-15R 4)5-15/20R HOTSWAP; 5-15/20P IN

PDUB20

Manufacturer Part Number
PDUB20
Description
UPS - Uninterruptible Power Supplies 4)5-15R 4)5-15/20R HOTSWAP; 5-15/20P IN
Manufacturer
Tripp Lite
Datasheet

Specifications of PDUB20

Power Rating
1920 W
Output Voltage Rating
100 V to 127 V
Number Of Outlets
4
Tower / Rackmount
Rackmount
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Specifications
OVERVIEW
Model Type
PDU Type
OUTPUT
Output Watt Capacity
(watts)
Frequency
compatibility
Output nominal voltage
Outlet quantity / type
INPUT
PDU Input Voltage
Recommended
Electrical Service
Maximum Input Amps
(A)
Input connection type
Plug Type
PDU Plug Type
Input cord length
details
Voltage compatibility
(VAC)
Phase
LEDS ALARMS & SWITCHES
Switches
Tripp Lite Hot-swap PDU systems support live-replacement of standard UPS systems for maintenance with no interruption of connected
server or networking loads
PDUB20 is universally compatible with any Tripp Lite or other brand of 100-127V UPS rated up to 2600VA or 1920 watts with a NEMA
5-15P or 5-20P input cable
2U horizontal rackmount form factor compatible with 2 or 4 post racks
Supports space saving rear-post mounting in the same rack space as many Tripp Lite Rackmount UPS systems (select installations, see
manual)
Pair of attached 5-20P PDU input cables connect to separate Utility and UPS power sources
4 5-15R and 4 5-15/20R outlets support critical networking loads in both Utility and UPS operating modes
One additional 5-15/20R pass-through outlet supports UPS input power cord
Dual input power cables support PDU connection to separate Utility and UPS power sources
Manual transfer switch with lighted status indicators controls the source of power to connected equipment between Utility and UPS
Set the switch to UPS during normal operation and connected equipment will receive full-time conditioned power from the UPS
Set the switch to Utility to bypass the UPS and provide connected equipment with unfiltered power directly from the Utility line cord while the
UPS system is removed and replaced with a fresh one
Once the new UPS is up and running with all connections restored, set the switch back to the UPS setting to once again provide
fully-conditioned UPS power to connected equipment
Hot-Swap
Hot-Swap
1920
50 / 60 Hz
100-127V
4 NEMA 5-15R and 4 5-15/20R outlets support critical connected loads; 1 designated pass-through 5-15/20R
outlet supports UPS 5-20P input plug (also supports UPS systems with 5-15P input connection)
100; 120; 127
100V, 120V, 127V
16
UTILITY & UPS input line cords both fitted with NEMA 5-20P input plug
Two NEMA 5-20P (20A 120V)
NEMA 5-20P
Utility input cable (10 ft / 3m) / UPS input cable (6 ft / 1.8m)
100-127
Single-Phase
Manual 2 position transfer switch offers fast switching between UPS and Utility operating modes in less than 6
milliseconds