2866682 Phoenix Contact, 2866682 Datasheet - Page 2

Linear & Switching Power Supplies QUINT SFB 1PHASE 48V DC 10A

2866682

Manufacturer Part Number
2866682
Description
Linear & Switching Power Supplies QUINT SFB 1PHASE 48V DC 10A
Manufacturer
Phoenix Contact
Type
Industrialr
Datasheet

Specifications of 2866682

Product
Switching
Commercial/medical
Commercial
Output Power Rating
41 W
Input Voltage
100 VAC to 240 VAC
Number Of Outputs
1
Output Voltage (channel 1)
48 V
Output Current (channel 1)
10 A
Mounting Style
DIN Rail
Dimensions
122 mm L x 130 mm W x 93 mm H
Open Frame/enclosed
Enclosed
Brand/series
QUINT-PS
Configuration
Enclosed
Mounting Type
DIN Rail
Operation
Switching
Output
48V @ 10 A
Phoenix Part Number
QUINT-PS/1AC/48DC/10
Primary Type
AC-DC
Voltage, Input
85 - 264/90 - 350 VAC/VDC
Voltage, Output
48 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
QUINT-PS/ 1AC/48DC/10
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866682
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Technical data
Input data
Nominal input voltage
AC input voltage range
DC input voltage range
Short-term input voltage
AC frequency range
DC frequency range
Current consumption
Inrush surge current
Power failure bypass
Input fuse
Name of protection
Protective circuit/component
Output data
Nominal output voltage
Setting range of the output voltage
Output current
Derating
Connection in parallel
Connection in series
Current limitation
Control deviation
Residual ripple
Maximum power dissipation idling
Power loss nominal load max.
General data
Width
Order No.: 2866682
100 V AC ... 240 V AC
85 V AC ... 264 V AC
90 V DC ... 350 V DC (UL 508: 90...250 V DC)
300 V AC
45 Hz ... 65 Hz
0 Hz
Approx. 5.1 A (120 V AC)
Approx. 2.3 A (230 V AC)
< 20 A (typical)
> 20 ms (120 V AC)
> 20 ms (230 V AC)
12 A (slow-blow, internal)
Transient surge protection
Varistor
48 V DC ±1%
30 V DC ... 56 V DC (> 48 V constant capacity)
10 A (-25 °C ... 60 °C)
13 A (with POWER BOOST, -25°C ... 40°C permanent)
60 A (with SFB technology, 12 ms)
From +60°C to 70°C: 2.5% per Kelvin
Yes, for redundancy and increased capacity
Yes
I
< 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
< 80 mV
16 W
41 W
90 mm
BOOST
= 13 A (for short circuit), approximately
PP
(with nominal values)
May 13, 2010
Page 2 / 7