HIH-4020-001 Honeywell, HIH-4020-001 Datasheet

no-image

HIH-4020-001

Manufacturer Part Number
HIH-4020-001
Description
Board Mount Humidity Sensors - 40 C to + 85 C Humidity Sensors
Manufacturer
Honeywell
Datasheet

Specifications of HIH-4020-001

Rh Range
0 % to 100 %
Rh Accuracy
3 %
Package / Case
SIP
Output Type
Analog
Supply Voltage (max)
5.8 V
Supply Current
500 uA
Maximum Operating Temperature
+ 85 C
Minimum Operating Temperature
- 40 C
Mounting Style
Through Hole
Lead Free Status / RoHS Status
Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
HIH-4020-001
Manufacturer:
HONEYWELL
Quantity:
50
HIH-4010/4020/4021
Series
Humidity Sensors
DESCRIPTION
The HIH-40104020/4021 Series Humidity Sensors are
designed specifically for high volume OEM (Original Equipment
Manufacturer) users.
Direct input to a controller or other device is made possible by
this sensor’s near linear voltage output. With a typical current
draw of only 200 µA, the HIH-4010/4020/4021 Series is often
ideally suited for low drain, battery operated systems.
Tight sensor interchangeability reduces or eliminates OEM
production calibration costs. Individual sensor calibration data
is available.
The HIH-4010/4020/4021 Series delivers instrumentation-
quality RH (Relative Humidity) sensing performance in a
competitively priced, solderable SIP (Single In-line Package).
FEATURES
Molded thermoset plastic housing
Near linear voltage output vs %RH
Laser trimmed interchangeability
Low power design
Enhanced accuracy
Fast response time
Stable, low drift performance
Chemically resistant
The HIH-4010 is an uncovered integrated humidity sensor, the
HIH-4020 is a covered integrated circuit humidity sensor, and
the HIH-4021 is a covered, condensation-resistant, integrated
circuit humidity sensor. All three products are available in two
lead space configurations.
The RH sensor is a laser trimmed, thermoset polymer
capacitive sensing element with on-chip integrated signal
conditioning.
The sensing element's multilayer construction provides
excellent resistance to most application hazards such as
wetting, dust, dirt, oils and common environmental chemicals.
Both products are available in two lead spacing configurations,
as well as with or without calibration and data printouts.
POTENTIAL APPLICATIONS
Refrigeration equipment
HVAC (Heating, Ventilation and Air Conditioning)
equipment
Medical equipment
Drying
Metrology
Battery-powered systems
OEM assemblies

Related parts for HIH-4020-001

HIH-4020-001 Summary of contents

Page 1

... Manufacturer) users. Direct input to a controller or other device is made possible by this sensor’s near linear voltage output. With a typical current draw of only 200 µA, the HIH-4010/4020/4021 Series is often ideally suited for low drain, battery operated systems. Tight sensor interchangeability reduces or eliminates OEM production calibration costs ...

Page 2

... General Notes: • Sensor is ratiometric to supply voltage. • Extended exposure to >90% RH causes a reversible • Sensor is light sensitive. For best performance, shield For HIH-4010-001/002/003/004 catalog listings only. For HIH-4020-001/002/003/004 and HIH-4021-001/002/003/ 004 catalog listings only. - zero offset)/slope OUT - 0.958)/0.0307 OUT (0 ...

Page 3

... FIGURE 1. OPERATING ENVIRONMENT (Non-condensing environment for HIH-4010 and HIH-4020 catalog listings only.) FIGURE 2. STORAGE ENVIRONMENT (Non-condensing environment for HIH-4010 and HIH-4020 catalog listings only.) Humidity Sensors Honeywell Sensing and Control 3 ...

Page 4

... HIH-4010/4020/4021 Series FIGURE 3. TYPICAL OUTPUT VOLTAGE VS RELATIVE HUMIDITY (At 25 ºC and 5 V.) 4 3.5 3 2.5 2 1.5 1 0.5 0 FIGURE 4. TYPICAL OUTPUT VOLTAGE (BFSL) VS RELATIVE HUMIDITY (At 0 ºC, 70 ºC and 5 V.) 4.5 4 3.5 3 2.5 2 1 Relative Humidity (%RH Relative Humidity (%) Sensor Response Sensor Response ...

Page 5

... FIGURE 5. HIH-4010 MOUNTING DIMENSIONS (For reference only. mm/[in]) FIGURE 6. HIH-4020 MOUNTING DIMENSIONS (For reference only. mm/[in]) Humidity Sensors Honeywell Sensing and Control 5 ...

Page 6

... HIH-4010/4020/4021 Series FIGURE 7. HIH-4021 MOUNTING DIMENSIONS (For reference only. mm/[in]) ...

Page 7

... Integrated circuit humidity sensor, 2,45 mm [0.100 in] lead pitch SIP, calibration and data printout HIH-4010-004 Integrated circuit humidity sensor, 1.27 mm [0.050 in] lead pitch SIP, calibration and data printout HIH-4020-001 Covered integrated circuit humidity sensor, 2,45 mm [0.100 in] lead pitch SIP HIH-4020-002 Covered integrated circuit humidity sensor, 1.27 mm [0.050 in] lead pitch SIP HIH-4020-003 Covered integrated circuit humidity sensor, 2, ...

Page 8

... In no event shall Honeywell be liable for consequential, special, or indirect damages. While we provide application assistance personally, through our literature and the Honeywell web site the customer to determine the suitability of the product in the application. Specifications may change without notice. The information we supply is believed to be accurate and reliable as of this printing ...