MY4-02-AC110-120 Omron, MY4-02-AC110-120 Datasheet - Page 13

General Purpose / Industrial Relays 4PDT 5A 110/120VAC

MY4-02-AC110-120

Manufacturer Part Number
MY4-02-AC110-120
Description
General Purpose / Industrial Relays 4PDT 5A 110/120VAC
Manufacturer
Omron
Series
MYr
Datasheet

Specifications of MY4-02-AC110-120

Contact Form
4PDT
Coil Voltage
110 VAC / 120 VAC
Contact Rating
5 A
Contact Termination
Solder Terminal
Mounting Style
Socket
Power Consumption
0.9 VA to 1.1 VA
Contact Material
Silver with Gold Flash
Coil Current
8.4 mA, 9.2 mA
Coil Type
Standard
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
02 110/120AC MY4 MY402110120AC,
MY
Characteristic Data
Without RC circuit
Push-to-test button
MY 12
Note: The dimension drawings show the 4-pole type. The dimensions of the 2- and 3-pole types are identical to the 4-pole type.
Diode Surge Suppression
Specifications and dimensions same as the standard
type with the following exceptions.
Terminal arrangement/internal connections: MY2(N)-
D(2) is the same as the MY4(N)-D(2) with the exception
of the contact configuration.
Ambient operating temperature: -55 to 60 C (-67 to
140 F).
Note: 1. Pay special attention to the polarities when using the DC type.
Connecting sockets
Use the standard MY4 (4PDT) sockets with the terminal arrangements listed below.
Terminal arrangement/Internal connections (Bottom view)
AC
Note: 1. R is a resistor for ampere-turn compensation, and is incorporated in the relays rated at 50 VAC or above.
2. The release time is somewhat longer, but satisfies the standard specifications of 25 ms.
3. The reverse-breakdown voltage of the diode is 1,000 VDC.
4. Available on DC versions only.
2. Pay attention to the polarity of the set and reset coils, as incorrect connection of positive and negative terminals will result in
malfunctioning of the relay.
DC
Terminal arrangement/Internal connections (Bottom view)
MY4-D
6, 12, 24, 48
100/110 VDC
With RC circuit
Mounting holes
When mounting the relay, use the connecting socket PYC-P2 shown
in “ACCESSORIES” section. The mounting hole dimensions shown
here are applicable to the relay with mounting stud.
MY4N-D2
6, 12, 24, 48 VDC
MY4N-D2
100/110 VDC
MY
13