SH48A50 TELEDYNE, SH48A50 Datasheet - Page 7

Solid State Relays 50A 24-510VAC Load 20-265VAC/DC Zero X

SH48A50

Manufacturer Part Number
SH48A50
Description
Solid State Relays 50A 24-510VAC Load 20-265VAC/DC Zero X
Manufacturer
TELEDYNE
Datasheets

Specifications of SH48A50

Control Voltage Range
20 VAC/DC to 265 VAC/DC
Load Voltage Rating
24 VAC to 510 VAC
Load Current Rating
50 A
Mounting Style
SMD/SMT
Relay Type
HIPpak Solid State
Application
Used for high inductive loads or phase angle control applications
Brand/series
SH Series
Current, Leakage, Off-state
3 mA
Current, Rating
50 A
Current, Surge
720 A (Max.)
Dimensions
1.77 in. L x 0.29 in. W x 2.3 in. H
Function
Soft Start
Resistance, Thermal, Junction To Case
0.45 °C⁄W
Standards
cULus, CE
Temperature, Ambient, Maximum
80 °C
Temperature, Ambient, Minimum
-40 °C
Termination
Screw
Voltage, Control
265 VAC/VDC
Voltage, Rating
510 VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
SH48A50
Manufacturer:
Teledyne Relays
Quantity:
135
© 2008 TELEDYNE RELAYS
Typical Loads (Random)
SH relays with random turn-on are designed for high inductive loads or phase angle control applications.
Our data sheet lists nominal current of power thyristors corresponding to a resistive load (AC-51).
Depending on the loads, check the inrush current at turn ON and possible overvoltages at turn OFF.
Main applications:
• AC-55b — Incandescent or infrared lamps. Inrush current is generally 10 times In during few 10ms. Random relays often use in-
• AC-53 — Three-phase motors. 2 or 3 random turn-on relays can drive such motors.
• AC-56a — Transformer loads. Very high inrush current up to 100 times In. Use a random turn-on SSR like the SH.
The table below lists recommended current values for proper lifetime expectancy.
Typical Loads (Zero-Cross)
SH relays with zero-cross turn-on are designed for most types of loads.
Our data sheet lists the AC-51 current value corresponding to resistive loads.
For other loads, check the inrush current at turn ON and possible overvoltages at turn OFF:
• AC-55b — Incandescent lamps. Inrush current is generally 10 times In during few 10ms.
• AC-55a — Electric discharge lamp. These loads often have overcurrent at turn ON and overvoltage at turn OFF, so use 400VAC
• AC-58 — One-pole motors. These loads often have overcurrent at turn ON and overvoltage at turn OFF, so use 400VAC SSR on
• AC-53 — Three-phase motors. 2 or 3 SH zero-cross relays can drive these motors, but generally use E3P/E3PT or other three-
• AC-56a — Transformer loads. Very high inrush current up to 100 times In. Use SH random relay or peak control SSR.
• AC-56b — Capacitor loads with very high current at turn ON and overvoltage at turn OFF. Our high-voltage relays are well adapted
Teledyne P/N DL12
phase angle controllers or soft-starters with the right control.
SSR on 230VAC mains.
230VAC mains and adapt the SSR current to the starting current of the motor.
phase relays or SH random range.
for high inrush current.
Teledyne P/N FW151
DIN Rail Adapter
2–2.5°C/W
SSR Model
125A
12A
25A
35A
50A
75A
95A
Mounting
HIPpak SSRs must be mounted on heat
sinks. A large range of heat sinks is
available. For heat-sink mounting, use
thermal grease or a thermal pad with high
conductibility specifi ed by Teledyne.
Teledyne P/N FW108
AC-53 Current
(motor)
2.5A
12A
16A
24A
32A
5A
9A
1.1°C/W
(800) 284-7007 • www.teledynerelays.com
AC-55b Current
(lamp)
2.5A
Teledyne P/N FW031
12A
16A
24A
32A
5A
9A
High Industrial Performance (HIPpak) Solid-State Relays
0.3°C/W
Teledyne P/N –12
Thermal Pad
AC-55b Current
(transformer)
0.4A
12A
1A
2A
3A
6A
9A
Output to 125A, 690 Vac
NEW Series SH
AC-55b Current
(capacitor)
XXX
XXX
XXX
13A
24A
36A
48A
SH\102008\Q4
SH Page 7