2868541 Phoenix Contact, 2868541 Datasheet - Page 2

POWER SUPPLY 6.5A 5VDC

2868541

Manufacturer Part Number
2868541
Description
POWER SUPPLY 6.5A 5VDC
Manufacturer
Phoenix Contact
Series
Stepr
Type
Industrialr
Datasheets

Specifications of 2868541

Voltage - Output
5V
Number Of Outputs
1
Power (watts)
32.5W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
5 VDC @ 6.5A
Size / Dimension
2.40" L x 2.83" W x 3.54" H (61mm x 72mm x 90mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
32.5W
Efficiency
80%
Approvals
cUL, EN, IEC, UL, VDE
Product
Switching
Commercial/medical
Commercial
Output Power Rating
33 W
Input Voltage
100 VAC to 240 VAC
Output Voltage (channel 1)
5 V
Output Current (channel 1)
6.5 A
Mounting Style
DIN Rail
Output Type
AC/DC Converter
Brand/series
STEP
Configuration
Enclosed
Operation
Switching
Output
5 V @ 6.5 A
Phoenix Part Number
STEP-PS/1AC/ 5DC/6.5
Power, Output
32.5 W
Primary Type
AC-DC
Voltage, Input
100 to 240 VAC
Voltage, Output
5 VDC
Flexible Assembly
Snaps-On to DIN-Rail or Direct Panel Mounting
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-2138
STEP-PS/1AC/ 5DC/6.5
STEP-PS/ 1AC/ 5DC/6.5
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2868541
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Technical data
Input data
Nominal input voltage
AC input voltage range
DC input voltage range
AC frequency range
DC frequency range
Current consumption
Inrush surge current
Power failure bypass
Input fuse
Permissible backup fuse
Type of protection
Protective circuit/component
Output data
Nominal output voltage
Setting range of the output voltage
Output current
Derating
Connection in parallel
Connection in series
Control deviation
Residual ripple
Peak switching voltages nominal load
Maximum power dissipation idling
Power loss nominal load max.
Order No.: 2868541
100 V AC ... 240 V AC
85 V AC ... 264 V AC
95 V DC ... 250 V DC
45 Hz ... 65 Hz
0 Hz
Approx. 0.5 A (120 V AC)
Approx. 0.3 A (230 V AC)
< 15 A (typical)
> 25 ms (120 V AC)
> 140 ms (230 V AC)
3.15 A (slow-blow, internal)
B6
B10
B16
Transient surge protection
Varistor
5 V DC ±1%
4 V DC ... 6.5 V DC (> 5 V constant capacity)
6.5 A (-25°C ... 55°C)
7.1 A (-25 °C ... 40 °C permanent)
11.5 A (maximum output current)
+55°C to +70°C: 2.5% per Kelvin
55 °C ... 70 °C 2.5%/K
Yes, for redundancy and increased capacity
Yes
< 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
< 50 mV
< 40 mV
< 0.4 W
8.1 W
PP
PP
(20 MHz)
(20 MHz)
Oct 8, 2010
Page 2 / 6

Related parts for 2868541