VARISTOR THERMAL 320VRMS 20MM

ETFV20K320E2

Manufacturer Part Number
ETFV20K320E2
Description
VARISTOR THERMAL 320VRMS 20MM
Manufacturer
EPCOS Inc
Series
ThermoFuser
Datasheet

Specifications of ETFV20K320E2

Varistor Voltage
510V
Current-surge
10kA
Number Of Circuits
1
Maximum Ac Volts
320VAC
Maximum Dc Volts
420VDC
Energy
273J
Package / Case
Disc 20mm
Product
MOV
Voltage Rating Dc
420 V
Voltage Rating Ac
320 V
Clamping Voltage
840 V
Peak Surge Current
10 KA
Surge Energy Rating
273 J
Capacitance
540 pF
Operating Temperature Range
- 40 C to + 85 C
Mounting
Through Hole
Dimensions
20 mm Dia. x 9.7 mm W x 25.7 mm L x 25.7 mm H
Lead Spacing
5 mm
Termination Style
Through Hole
Tolerance
10 %
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
495-3645
Reliability data
Test
Varistor voltage
Clamping voltage
Surge current derating,
8/20 s
Surge current derating,
2 ms
Abnormal overvoltage
test
Please read Cautions and warnings and
Important notes at the end of this document.
Housed varistors
ThermoFuse varistors, ETFV20 series
Test methods/conditions
The voltage between two terminals with
the specified measuring current applied
is called V
The maximum voltage between two
terminals with the specified standard
impulse current (8/20 µs) applied.
CECC 42 000, test C 2.1
100 surge currents (8/20 µs), unipolar,
interval 30 s, amplitude corresponding
to derating curve for 100 impulses at
20 µs
CECC 42 000, test C 2.1
100 surge currents (2 ms), unipolar,
interval 120 s, amplitude corresponding
to derating curve for 100 impulses at 2
ms
UL1449, limited current abnormal
overvoltage test. Apply a high AC
voltage to ThermoFuse varistor, the
amplitude of overvoltage and current
limit will be adopted from UL1449
general instruction in section 37. The
specimen will be tested on a softwood
surface covered with a double layer of
white tissue paper. The specimen is to
be loosely draped with a double layer
of cheesecloth.
The cheesecloth shall cover openings
where flame, molten or other particles
may be expelled as a result of the test.
The test result will be visually
inspected.
V
(1 mA
DC
Page 5 of 10
@ 0.2 ... 2 s).
Requirement
To meet the specified value
To meet the specified value
| V/V (1 mA)| 10%
(measured in direction of
surge current)
No visible damage
| V/V (1 mA)| 10%
(measured in direction of
surge current)
No visible damage
Any of these phenomena shall
not be observed, or this
specimen will be judged as
failed part.
1.
2.
3.
4.
Emission of flame, molten
metal, glowing or flaming
particles through any
openings (pre-existed or
created as a result of the
test) in the product.
Charring, glowing, or
flaming of the supporting
surface, tissue paper, or
cheesecloth.
Ignition of the enclosure.
Creation of any openings
in the enclosure that
result in accessibility of
live parts, when judged in
accordance with
accessibility of live parts,
UL1449 section 13.
ETFV20