LPJ-40SP Cooper/Bussmann, LPJ-40SP Datasheet - Page 3

no-image

LPJ-40SP

Manufacturer Part Number
LPJ-40SP
Description
FUSE 40A 600V T-LAG CLASS J
Manufacturer
Cooper/Bussmann
Series
LPJr
Type
Generalr
Datasheets

Specifications of LPJ-40SP

Fuse Type
Slow Blow, Time Lag
Voltage - Rated
600VAC
Current
40A
Package / Case
Cylindrical
Size / Dimension
1.060" Dia x 2.380" L (26.92mm x 60.45mm)
Mounting Type
Holder
Current Rating
40 Amps
Voltage Rating
600 Volts
Fuse Size / Group
Class J
Termination Style
Cartridge
Dimensions
2 3/8 in L x 1 1/16 in W
Product
Industrial Power Fuse
Interrupt Rating
300 KAmps
Brand/series
Low-Peak®/LPJ Series
Class
Class J
Color
Yellow
Current, Rating
40 A
Current, Ratings
40 A
Diameter
1.06 in.
Length
2.38 in.
Primary Type
Cylinder
Termination
Cartridge
Voltage, Rating
600/300 VAC/VDC
Time Delay
10 Seconds (Min.) at 500% Rated Current
Operating Temperature
-
Dc Cold Resistance
-
Melting I²t
-
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Operating Temperature
-
Color
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
Q2199353A

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
LPJ-40SP
Manufacturer:
Cooper Bussmann
Quantity:
5 000
Part Number:
LPJ-40SP
Manufacturer:
BUSS
Quantity:
20 000
Bussmann
®
LOW-PEAK
®
LPJ
Dual-Element Time-Delay Fuses
1-60 Amps
Class J – 600 Volt
Current Limitation Curves
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained
in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Form No. LPJ 1-60
Page 3 of 3
Data Sheet: 1006
10-2-02
SB02295

Related parts for LPJ-40SP