DA2-B0-34-615-121-C Carling Technologies, DA2-B0-34-615-121-C Datasheet - Page 2

CIRCUIT BREAKR MAG 15A DINRAILMT

DA2-B0-34-615-121-C

Manufacturer Part Number
DA2-B0-34-615-121-C
Description
CIRCUIT BREAKR MAG 15A DINRAILMT
Manufacturer
Carling Technologies
Series
Dr
Datasheet

Specifications of DA2-B0-34-615-121-C

Breaker Type
Hydraulic-Magnetic
Voltage
65VDC,480VAC
Current - Trip (it)
15A
Number Of Poles
2
Actuator Type
Lever
Mounting Type
DIN Rail
Product Type
Circuit Breakers
Current Rating
15 Amps
Voltage Rating
277 VoltsAC / 80 VoltsDC
Trip Time
0.6 s to 20 s
Mounting Style
DIN Rail
Termination Style
Screw
Circuit Function
Series Trip (Current)
Product
Hydraulic Magnetic Circuit Breakers
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
432-1030
www.carlingtech.com
Electrical
Maximum Voltage
Standard Current Coils
Standard Voltage Coils
Insulation Resistance
Dielectric Strength
Resistance, Impedance
Pulse Tolerance Curves
AC, 480 wye/277 VAC (See Table
A), 50/60 Hz, 65VDC
0.100, 0.250, 0.500, 0.750, 1.00,
2.50, 5.00, 7.50, 10.0, 15.0, 20.0,
25.0, 30.0, 35.0, 40.0 & 50.0.
Other ratings available - consult fac-
tory.
DC - 6V, 12V; AC - 120V, other rat-
ings available, see ordering scheme.
Minimum of 100 Megohms at 500
VDC.
UL, CSA: 1960 V 50/60 Hz for one
minute between all electrically isolat-
ed terminals. D-Series circuit break-
ers comply with the 8mm spacing
and 3750V 50/60 Hz dielectric
requirements from hazardous volt-
age to operator accessible surfaces
and between adjacent poles per
Publications EN 60950 and VDE
0805.
Values from Line to Load Terminal -
based on Series Trip Circuit Breaker
Mechanical
Endurance
Trip Free
Trip Indication
Physical
Number of Poles
Internal Circuit Config.
Weight
Standard Colors
Mounting
Environmental
Designed and tested in accordance with requirements of specifi-
cation MIL-PRF-55629 & MIL-STD-202 as follows:
Shock
Vibration
Moisture Resistance
Salt Spray
Thermal Shock
Operating Temperature
D-Series – General Specifications
10,000 ON-OFF operations @ 6 per
minute; with rated Current and
Voltage.
All D-Series Circuit Breakers will trip
on overload, even when actuator is
forcibly held in the ON position.
The operating actuator moves posi-
tively to the OFF position when an
overload causes the breaker to trip.
Rocker Type: 1-3; Handle Type: 1-4
Switch Only and Series Trip with
current or voltage trip coils.
Approximately 128 grams/pole
(Approximately 4.57 ounces/pole)
Housing - Black; Actuator - See
Ordering Scheme.
Mounts on a standard 35mm
Symmetrical DIN Rail (35 x 7.5 or 35
x 15mm per DIN EN5002).
Withstands 100 Gs, 6ms, sawtooth
while carrying rated current per
Method 213, Test Condition "I".
Instantaneous and ultra-short curves
tested @ 90% of rated current.
Withstands 0.060" excursion from
10-55 Hz, and 10 Gs 55-500 Hz, at
rated current per Method 204C, Test
Condition A. Instantaneous and
ultra-short curves tested at 90% of
rated current.
Method 106D, i.e., ten 24-hour
cycles @ + 25°C to +65°C, 80-98%
RH.
Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Method 107D, Condition A (Five
cycles @ -55°C to +25°C to +85°C
to +25°C).
-40° C to +85° C
97