3500-P10-10A E-T-A, 3500-P10-10A Datasheet

no-image

3500-P10-10A

Manufacturer Part Number
3500-P10-10A
Description
CIRC BRKR MAGNETIC .250QC 10A
Manufacturer
E-T-A
Series
3500r
Datasheet

Specifications of 3500-P10-10A

Breaker Type
Thermal-Magnetic
Voltage
65VDC, 250VAC
Current - Trip (it)
10A
Number Of Poles
1
Actuator Type
Push to Reset
Mounting Type
Panel Mount
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
3500-P10-10AMP
Q4478678
Single pole thermal-magnetic circuit breaker with tease-free, trip-free,
snap action mechanism and two button operation (M-type TM CBE
to EN 60934). Featuring a flange for panel mounting, and optional
auxiliary contacts and unprotected shunt tap terminal. Type 4000 offers
lower internal resistance values and is fitted as standard with auxiliary
contacts and an intermediate reset position in which all contacts are
isolated.
Approved to CBE standard EN 60934 (IEC 60934).
Control systems, instrumentation, medical equipment, machine tools,
robotics, communications systems.
Type No.
3500
4000
3500 - .. - P10 - A3 - Si - 10 A
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Current
ratings (A) 3500
0.05
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.5
2
2.5
Issue B
Description
Typical applications
Ordering information
Standard current ratings and typical internal resistance values
standard version
low resistance version
Mounting (optional)
F11
flange with additional M3 insertion nuts
Terminal design
P10
K20
Internal resistance (Ω)
447
131
40
19.3
10.4
7.1
4.3
2.5
1.67
0.61
0.38
0.24
blade terminals 6.3-0.8 (QC .250), tinned
screw terminals M3.5x5.5 with clamp
(not with -Si or type 4000)
Shunt terminal (optional)
A3
Thermal-Magnetic Circuit Breakers 3500/4000
same as main terminals
(up to I
Auxiliary contacts (optional with type 3500)
Si
ZR-Si
4000
211
48
12.4
5.4
3.1
2.0
1.32
0.76
0.49
0.21
0.101
0.078
auxiliary contacts, silver plated
terminals one each N/O and N/C
auxiliary contacts with intermediate
position (standard with type 4000)
Current ratings
0.05...16 A
0.05...10 A
N
= 7 A, max. load 5 A)
ordering example
Current
ratings (A) 3500
3
4
5
6
7
8
10
12
14
15
16
(type 3500)
(type 4000)
Internal resistance (Ω)
0.19
0.090
0.061
0.041
0.034
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
4000
0.054
0.035
0.025
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
www.e-t-a.com
Current rating range
Dielectric strength
(IEC 60664 and 60664A)
Interrupting capacity
Humidity
For further details please see chapter: Technical Information
Voltage rating
Auxiliary circuit
Typical life
Ambient temperature
Insulation co-ordination
(IEC 60664 and 60664 A)
Insulation resistance
Interrupting capacity I
(UL 1077)
Degree of protection
(IEC 60529/DIN 40050)
Vibration
Shock
Corrosion
Mass
Authority
3500:
VDE (EN 60934)
CSA, UL
UL
4000:
VDE (EN 60934)
CSA
Technical data
Approvals
operating area
main/aux. circuit
aux. circuit 4-5/6-7
type 3500:
3500
standard type
cn
Voltage ratings
AC 240 V; DC 65 V
AC 250 V; DC 80 V
DC 65 V
AC 240 V; DC 65 V
AC 250 V; DC 80 V
AC 240 V, 50/60 Hz; DC 65 V
(UL: AC 250 V; DC 80 V)
3500: 0.05...16 A
4000: 0.05...10 A
1 A, AC 240 V / DC 65 V
5,000 operations at 1 x I
5,000 operations at 2 x I
-30...+60 °C (-22...+140 °F)
rated impulse
withstand voltage
2.5 kV
reinforced insulation in operating area
test voltage
AC 3,000 V
AC 1,500 V
AC 840 V
> 100 MΩ (DC 500 V)
3500
0.05...0.8 A
1...2 A
2.5...16 A
I
0.05...16 A
0.05...16 A
operating area IP40
terminal area IP00
5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
25 g (11 ms) to IEC 60068-2-27, test Ea
96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
approx. 40 g
N
low-resistance type
4000
4000
0.05...0.2 A
0.3...2 A
2.5...10 A
U
AC 250 V
DC 80 V
N
Current ratings
0.05...16 A
0.05...16 A
0.05...25 A
0.05...10 A
0.05...10 A
pollution
degree
2
N
N
, inductive
, resistive
1,000 A
1,000 A
self-limiting
200 A
400 A
2 - 53
2

Related parts for 3500-P10-10A

3500-P10-10A Summary of contents

Page 1

... A (type 3500) 0.05...10 A (type 4000) 3500 - .. - P10 - ordering example The exact part number required can be built up from the table of choices shown above. Ordering references for optional features should be omitted if not required. Standard current ratings and typical internal resistance values Current Internal resistance (Ω ...

Page 2

... Thermal-Magnetic Circuit Breakers 3500/4000 Dimensions Version -P10 ø8.5 .335 2 42 1.65 current rating 1.97 29 1.14 20 .787 5 58 2.28 Installation drawing (reinforced insulation) 1 .039 Internal connection diagrams 4 .157 Switching position with intermediate position and auxiliary contacts (-ZR-Si) 11.5 line 1 .453 blade terminals DIN 46244-A6 ...

Page 3

... Magnetic tripping currents are increased by 20 supplies. 2) Magnetic tripping currents are decreased by 20 supplies. Issue B Typical time/current characteristics 3500 8 … 10000 1000 100 10 1 0.1 0.01 0.001 ...

Page 4

... Thermal-Magnetic Circuit Breakers 3500/4000 Special version 3500-...-2100 Single pole thermal-magnetic overcurrent circuit breaker with slow magnetic trip curve, suitable for high inrush currents ( Suffix -2100 is also available for types 3400 and 3600. Enquire for further details. Typical applications Industrial control systems, telecommunications, etc. ...

Related keywords