CTB-B-B-05 Carling Technologies, CTB-B-B-05 Datasheet - Page 6

CIRCUIT BREAKER ROCKER 5A SP BK

CTB-B-B-05

Manufacturer Part Number
CTB-B-B-05
Description
CIRCUIT BREAKER ROCKER 5A SP BK
Manufacturer
Carling Technologies
Series
CTBr
Datasheets

Specifications of CTB-B-B-05

Breaker Type
Thermal
Voltage
50VDC, 125/250VAC
Current - Trip (it)
5A
Number Of Poles
1
Actuator Type
Rocker
Mounting Type
Panel Mount
Product Type
Circuit Breakers
Current Rating
5 Amps
Voltage Rating
250 VoltsAC / 32 VoltsDC
Trip Time
2.2 s to 15 s
Mounting Style
Through Hole
Termination Style
Quick Connect
Color
Black
Dielectric Strength
1500 Volts
Illuminated
No
Length
38.99 mm
Product
Thermal Circuit Breakers
Width
13.71 mm
Diameter, Disc
0.540 in. (Max.)
Resistance
100 Megohms (Insulation)
Thickness
0.032 in. to 0.062 in. (Panel)
Tolerance
± 0.005%
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
432-1126
4
Breaker must hold 100% of rated current and must trip at 150% and above, within the time limits shown in curve. Trip times specified at 25° ambient with no preloading.
1. To adjust the breaker rating for ambient temperature multiply the breaker rating by the factor. (ex: 5 amp rating at 0°C: 5 x .67 = 3.3 amp. Select 3 amp rating.)
CMB-Series Pushbutton Thermal Circuit Protector
Trip Time in Seconds
Trip Curves
Rating:
3 to 20A, 125-250VAC, 32VDC
Approvals:
UL, CUL, CSA, TUV, CE
UL1500/ISO8846 for ignition
protection/marine
Dielectric Strength:
2500 VAC/ 1 minute
Interrupting capacity:
2500 amps
Insulation Resistance:
100M ohms
Operating Temperature:
-10°C to 60°C
Voltage drop:
< 0.25 V
Applications:
Household Appliances
Transportation
Marine
Power Strips
Medical Equipment
Audio Visual Equipment
Power Supplies
ROHS Compliant
www.carlingtech.com