LPT60-M EMERSON-NETWORKPOWER [Emerson Network Power], LPT60-M Datasheet - Page 2

no-image

LPT60-M

Manufacturer Part Number
LPT60-M
Description
Medical safety approvals
Manufacturer
EMERSON-NETWORKPOWER [Emerson Network Power]
Datasheet
Environmental Specifications
Operating temperature:
Electromagnetic
susceptibility:
Humidity:
Vibration:
Storage temperature:
Temperature coefficient:
MTBF demonstrated:
Ordering Information
LPT62-M
LPT63-M
1. Peak current lasting <30 seconds with a maximum 10% duty cycle.
2 . At 25°C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings.
3 . Peak-to-peak with 20 MHz bandwidth and 10μF in parallel with a 0.1μF capacitor at rated line voltage and load ranges.
4. Minimum Loads are required.
Number
Model
Voltage
Output
+5V
+12V
-12V
+5V
+15V
-15V
Minimum
0.7A
0.3A
0A
0.7A
0.3A
0A
Load
0° to 50°C ambient derate each output at 2.5% per degree
from 50° to 70°C, -20°C startup
Designed to meet IEC 801, -2, -3, -4, -5, -6, Level 3
Operating; non-condensing 5% to 95%
Three orthogonal axes, sweep at 1 oct/min, 5 min. dwell
at four major resonances 0.75G peak 5 Hz to 500 Hz,
operational
-40° to 85°C
±.04% per °C
>550,000 hours at full load and 25°C ambient conditions
with Convnection
Maximum Load
cooling
7A
3A
0.7A
7A
2.8A
0.7A
Maximum Load
with 30CFM
Forced Air
8A
3.5A
1A
8A
3.3A
1A
Peak Load
10A
6A
1.5A
10A
4A
1.5A
1
Regulation
±2%
±5%
±5%
±2%
±5%
±5%
2
Ripple P/P (PARD)
50mV
120mV
120mV
50mV
150mV
150mV
3
Embedded Power for
Business-Critical Continuity
LPT60-M Series
Rev. 06.15.07
2 of 3

Related parts for LPT60-M