e5csv-q1tdac/dc24 ETC-unknow, e5csv-q1tdac/dc24 Datasheet - Page 10

no-image

e5csv-q1tdac/dc24

Manufacturer Part Number
e5csv-q1tdac/dc24
Description
Temperature Controllers
Manufacturer
ETC-unknow
Datasheet
(2) Using the E5CSV in Devices for Fahrenheit-scale Users
(Displaying in ° F)
Turn ON switch 6 to display temperatures in ° F.
Temperature Range for ° F
The temperature is set to ° F using the same temperature range switch as ° C.
Note: The control range for a thermocouple input or platinum resistance thermometer input is
Using K, L/Pt100 Thermometers
Turn ON switch 5 when using K, L/Pt100 Thermometers.
Note: The previous name J-DIN has been changed to L in accordance with revisions to DIN standards.
(3) Setting Input Shift
Turn ON switch 4, and after turning ON the power, press the Mode
Key until h0 (indicates input shift of 0) is displayed. Press the Up and
Down Keys to set the shift value.
10
Thermocouple
0
1
2
3
4
5
6
7
8
9
Set-
ting
The control range for multi-input (thermocouple/platinum resistance thermometer) models is
K
J/L
Temperature Controllers
° F
0 to 200
0 to 300
0 to 400
0 to 500
0 to 600
0 to 999
0 to 999
0 to 300
0 to 400
0 to 500
ON
ON
ON
1
1
1
2
2
2
3
3
3
4
4
4
Platinum Resistance
Thermometer
0
1
2
3
4
5
6
7
8
9
Set-
ting
5
5
5
JPt100
or
Pt100
E5CSV
6
6
6
° F
0.0 to 50.0
0.0 to 99.9
0.0 to 199.9
50 to 50
20 to 80
0 to 200
0 to 300
0 to 400
0 to 600
0 to 800
Multi-input (Thermocouple/
Platinum Resistance
Thermometer)
Control mode switch 5: OFF
0
1
2
3
4
5
6
7
8
9
Shift Example
Note: When control mode switch 4 is turned OFF (no input shift dis-
Set-
ting
Input shift display
h9 (+9° C shift)
l9 (
h0 (no shift)
play), the input shift is not displayed but the shift value is en-
abled. To disable input shift, set the input shift value to h0. The
shift range depends on the setting unit.
K
J
L
T
U
N
R
Setting unit
Compensation range
Input shift display
9° C shift)
° F
0.0 to 199.9
0.0 to 199.9
0.0 to 199.9
99 to 1999
99 to 1500
99 to 1500
99 to 700
99 to 700
99 to 1999
10% to +10% FS for each temperature range.
0 to 1999
40 to +40° F of each temperature range.
Measured temperature
1° C
L99 to H99
99 to +99° C
100° C
100° C
100° C
Multi-input (Thermocouple/
Platinum Resistance
Thermometer)
Control mode switch 5: ON
0
1
2
3
4
5
6
7
8
9
Set-
ting
Pt100
JPt100
9.9 to +9.9° C
L9.9 to H9.9
0.1° C
Temperature
99 to 1500
° F
0.0 to 199.9
0.0 to 199.9
display
99 to 99
99 to 900
99 to 99
100° C
109° C
91° C
0 to 200
0 to 400
0 to 200
0 to 400

Related parts for e5csv-q1tdac/dc24