Datasheet
25.3. B
Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called
return voltage immunity or resistance against Back- E.M.F. (Electro Magnetic Force).
This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power
supply. It does not matter, whether the power supply is on or off.
The maximum allowed feed back voltage is 63Vdc. The absorbing energy can be calculated according to the built-in
large sized output capacitor which is specified in chapter 8.
25.4. O
Standard miniature circuit breakers (MCBs) can be used for branch protection. Ensure that the MCB is rated for DC
voltage, too. The following tests show which circuit breakers the power supply typically trips.
Circuit breakers have huge tolerances in their tripping behavior. Therefore, these typical tests can only be used as a
recommendation or for comparing two different power supplies. Furthermore, the loop impedance has a major
influence on whether a breaker trips or not. Two tests were performed, representing typical situations:
Test 1: Short circuit with S1 on the power supply end of the cable (loop impedance approx. 20mOhm)
Test 2: Short circuit with S1 on the load end (additional impedance included; represents longer load wire length).
Example:
Which wire gauge must be used to trip a B-Characteristic circuit breaker with a rating of 6A? The load wire length is
21m.
Answer: A 6A B-Characteristic circuit breaker requires a loop impedance of less than 180mOhm (test results). The wire
length table shows that up to 25.1m wire with a cross section of 2.5mm
than 2.5mm
Nov. 2006 / Rev.1.1 DS-CS10.481-EN
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
AC
AC
Fig. 25-3 Branch protectors, test circuit 1
Fig. 25-4 Branch protectors, test circuit 2
Supply
Supply
Power
Power
ACK
DC
DC
UTPUT
2
shall be used.
+
+
-
-
-
FEEDING
C
Breaker
Breaker
Circuit
Circuit
I
I
C–Series
IRCUIT
S1
L
R
OADS
S1
B
www.pulspower.com Phone +49 89 9278 0
REAKERS
+
+
-
-
Load
Load
82mOhm
180mOhm
Parameters:
Input voltage:
The following circuit breaker tripped during the test:
A- or Z- Characteristic::
B- Characteristic:
C- Characteristic:
Parameters:
Input voltage:
The following circuit breaker tripped during the test:
A- or Z- Characteristic::
B- Characteristic:
C- Characteristic:
What does this resistance mean in wire length?
0.5mm
2.3m
5.0m
2
0.7mm
3.2m
7.0m
2
are below 180mOhm. A wire not smaller
Germany
2
230Vac, load current:
230Vac, load current:
48V, 5A, S
1.0mm
10.0m
4.6m
2
equal or smaller 25A
equal or smaller 16A
equal or smaller 10A
≤ 16A and R= 82mOhm
≤ 6A and R= 180mOhm
≤ 6A and R= 180mOhm
1.5mm
15.0m
6.9m
INGLE
2
CS10.481
2.5mm
11.4m
25.1m
P
HASE
0A
0A
2
I
4.0mm
NPUT
18.3m
40.1m
17/20
2