TS200-EX MORNSUN Science& Technology Ltd., TS200-EX Datasheet

no-image

TS200-EX

Manufacturer Part Number
TS200-EX
Description
Tsx00-ex Isolating Switching Barrier
Manufacturer
MORNSUN Science& Technology Ltd.
Datasheet
TSX00-EX
Isolating Switching Barrier
● Fitted devices: 1. NAMUR Sensors;
● Phase-angel and inverse control setting;
● Open circuit detection setting
● Respective Isolation(2,500VDC between
● Operation Temperature:-20°C ~ +60°C
● Reliable Performance (MTBF>1,000,000 Hours)
switch or approach switch’s status in locations
where hazardous exists; isolate, transmit and
output it to safe area. Input and output can be set
to inverse control. Approach switch open circuit
detection function.
Output/Power source.
Address: 2th floor 6th building, Huangzhou
Industrial District, Guangzhou, China
Tel: 86-20-38601850
Fax:86-20-38601272
Http://www.mornsun-power.com
FEATURES
APPLICATIONS
MODEL SELECTION
MORNSUN Science & Technology co.,Ltd.
TS100-EX
The copyright and authority for the interpretation of the products are reserved by Mornsun
Input/Output/Power source);
This Isolation Switching Barrier can detect
2. Mechanical Joints.
Isolation between Input/
Isolating barrier mark
Input/output mode
Channel number
Signal style
Product seriers
Under phase-angel control
(K1 “K2 OFF”)
Under inverse control
(K1”K2 ON”)
Open detection function
When connected with NAMUR
sensor
When connected with common
contact joint switch
Hazardous
PRODUCT PROGRAM
ELECTRICAL CHARACTERISTICS
TRANSMISSION CHARACTERISTICS
Note: K1 is setup channel1 to be reverse or not ,K2 is setup channel1 to be reverse or not
ISOLATION CHARACTERISTICS
Electrical isolation
Isolation strength
Surge Resist
EMC
parameter
Part number
TS200-EX
Safe Area
TS100-EX
Common
Area
Operation voltage
Power consumption
Power indicating
Input Signal
Output Voltage
Short circuit current
Input switching frequency
threshold
Output signal
Response time
driving capability
Load type
Typ.
24
Voltage(VDC)
Input(Power)
Three-port isolation (between signal input, signal output and power
supply)
2.5KVDC (test for 1minute, humidity < 70%)
5KV 1.2/50us (Based on IEC255-4)
EN61326
Range
18-36
Input loop current > 2.1mA, relay output close, channel
indicator light (yellow) ON
Input loop current < 1.2mA, relay output open, channel
indicator light (yellow) OFF
Input loop current > 2.1mA, relay output close, channel
indicator light (yellow) OFF
Input loop current < 1.2mA, relay output open, channel
indicator light (yellow) ON
Function when K3 is OFF
Input loop current < 0.05mA, open circuit alarm, channel
red indicator light ON
To achieve open circuit detection function, a 10KΩ resistor
must be connected to the switch in parallel
Output(Hazardous end)
Voltage
Specifications subject to change without notice.
8VDC
Typ.
18-36VDC
About 2.0W (with relay output OFF)
LED light (green) ON when operating
Switch status of NUMAR sensor,
mechanical joint etc
8V (Open status)
<8mA
<10Hz
Typ:1.55mA (hysteresis:0.2mA)
Relay output (1” ON” joint)
<20ms
250VAC / 3A or 30VDC / 3A
Resistive load
TSX00-EX
Short Circuit
< 8 mA
Current
A/1-2009
Relay output
Relay output
(Safe end)
Output
Page 1 of 3
numbers
Channel
1
2

Related parts for TS200-EX

TS200-EX Summary of contents

Page 1

... The copyright and authority for the interpretation of the products are reserved by Mornsun PRODUCT PROGRAM Input(Power) Output(Hazardous end) Part number Voltage(VDC) Typ. Range TS100-EX 24 18-36 TS200-EX ELECTRICAL CHARACTERISTICS Operation voltage Common Power consumption parameter Power indicating Input Signal Output Voltage Hazardous Area Short circuit current ...

Page 2

STANDARDS AND CERTIFICATIONS Explosion protection certification mark Explosion protection certification parameters Certified by: CHINA NATIONAL QUALITY SUPERVISION AND TEST CENTRE FOR EXPLOSION PROTECTED ELECTRICAL PRODUCTS No.:CNEx08.0003 OTHER CHARACTERISTICS Operation temperature:-20°C ~ +60°C Ambient temperature Transport and Storage temperature:-40°C ~ +85°C ...

Page 3

OUTLINE DIMENSIONS 13 Channel 1 Phase angle and inverse control setting Channel 2 Phase angle and inverse control setting 2 3 Open circuit alarm ...

Related keywords