AFM-11 UNITED AUTOMATION, AFM-11 Datasheet - Page 2

TRIGGER MODULE, PHASE ANGLE

AFM-11

Manufacturer Part Number
AFM-11
Description
TRIGGER MODULE, PHASE ANGLE
Manufacturer
UNITED AUTOMATION
Series
X10221r
Datasheet

Specifications of AFM-11

Supply Voltage
18V
Operating Temperature Range
0°C To +75°C
Approval Bodies
CE
External Depth
60mm
External Length / Height
43mm
External Width
92mm
Fixing Centres
80mm
For Use
RoHS Compliant
POWER CONNECTIONS
NOTE I
SPECIFICATIONS
Signal Span minimum
Signal Span maximum
Signal Zero offset
Signal input resistance
Trigger pulse height
Trigger pulse rating
Trigger isolation voltage
Trigger shorted output
FUSING
It is recommended to use semiconductor (fast acting) type fuses or circuit breakers (Semiconductor - MCB) for unit
protection and an appropriate safety fuse for the units supply (F1A). On initial ‘switch on’ some loads may need an
increased factor of safety (F of S) for unit and/or device protection. (See the SRA Datasheet for further information).
CE MARKING
This product family carries a “CE marking”. These phase angle controllers need a suitable remote filter. For information
see recommendation section and contact our sales desk. (See the Declaration of Conformity).
RECOMMENDATIONS
Other documents available on request, which may be appropriate for your application:-
CODE
X10229
X10213
X10255
AP02/4
edition of the I.E.E. wiring regulations (BS7671) by suitably qualified/trained personnel. The regulations contain important
requirements regarding safety of electrical equipment (For International Standards refer to I.E.C. directive IEC 950).
ORDER CODE
t is recommended that installation and maintenance of this equipment should be done with reference to the current
Optional extras include: Potentiometer, Supply transformer, complete assemblies, Filter.
When ordering a filter the current of the load is required.
IDENTITY
RFI
ITA
SRA
COS
1Southport Business Park
Kew
Southport, PR8 4HQ
ENGLAND
Page No. 2 of 2
UNITED AUTOMATION LIMITED
0 to 2.5V dc
0 to 25V dc
0 to 50% of span
5000
8V open circuit
250mA in to 10
2500V rms
Protected
± 20%
State part number:
DESCRIPTION
Filtering recommendations - addressing EMC Directive
Interaction, uses for phase angle and for burst fire control.
Safety requirements - addressing the Low Voltage Directive
(LVD) including:- Thermal data/cooling ; “Live” parts warning & Earth
requirements; Fusing recommendations.
UAL Conditions of sale.
Issue 4
Tel: 0044 (0) 1704 – 516500 Main
Tel: 0044 (0) 1704 – 516516 Sales
Fax: 0044 (0) 1704 – 516501
Enquiry@united-automation.com
AC input supply (nominal)
Auxiliary output (nominal)
Thyristor line voltage
Manual potentiometer
Limit feedback input
Soft start
Storage temperature
Operating temperature
AFM11
Date 20/04/00
18 to 24V rms @ 100mA
5V dc @ 20mA protected
110 to 480V rms @ 50/60 Hz
2K , 5K
0.6 - 30V dc
0-20 seconds
-20 C to +85 C
0 C to 75 C
2q
or 10K

Related parts for AFM-11