G4IDC15 OPTO 22, G4IDC15 Datasheet - Page 4

no-image

G4IDC15

Manufacturer Part Number
G4IDC15
Description
I/O Module
Manufacturer
OPTO 22
Type
Inputr
Datasheets

Specifications of G4IDC15

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Supply Voltage Min
10VDC
No. Of Digital Outputs
1
Signal Input Type
10 To 32VDC
Supply Voltage Max
32VDC
No. Of Outputs
1
No. Of Analog Inputs
1
Brand/series
G4 Series
Connection To Host
Backplane
Current Rating
50 mA
Current, Input
15 mA
Current, Leakage Output
100 μA
Current, Off-state
1 mA
Dimensions
48.8mmL×12.2mmW×41.1mmH
Input
10 to 32 VDC
Input Type
Digital
Input, Range
10 to 32 VDC
Mounting Type
PCB
Number Of Channels
1
Primary Type
Data Acquisition
Special Features
Optical Isolation
Standards
UL Recognized, CSA Certified, CE Marked, NEMA Approved
Temperature, Operating, Maximum
+70 °C
Temperature, Operating, Minimum
-30 °C
Time, Turn-off
5 ms
Time, Turn-on
5 ms
Voltage, Input
12 to 32 V
Voltage, Isolation
4000 V
Voltage, Logical
15 VDC
Voltage, Offset
3 V
Voltage, Rating
15 VDC
Voltage, Supply
15 VDC
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
PAGE
4
G4IDC5-SW and G4IDC5-SWNC Modules
Description
Each G4IDC5-SW and G4IDC5-SWNC module provides one isolated
channel of contact status input. Each module supplies 13 volts of
power to an external dry contact switch. The G4IDC5-SW senses
switch closure; the G4IDC5-SWNC senses switch opening. Each
user-supplied switch is connected with two wires. Because these
modules include power for the switch, they are particularly cost-
effective when labor costs for wiring external power are high.
Specifications
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com
© 2006 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
Field Side Ratings
Open Circuit Voltage (Switch Open)
Short Circuit Current (Switch Closed)
Minimum Off Resistance
Maximum Allowable On Resistance
(Wire + Contact Resistance)
Logic Side Ratings
Logic Output Voltage for G4IDC5-SW
(normally open)
Logic Output Voltage for G4IDC5-SWNC
(normally closed)
Maximum Operating Common Mode
Voltage (Field Term to Logic Connector)
Power Requirements:
Module Ratings
Number of Channels Per Module
Turn-on Time
Turn-off Time
Input-to-output Isolation (transient)
Temperature
11 VDC min., 13 VDC typical, 15 VDC max.
6 milliamps nominal
≥20 K ohms
500 ohms
<0.5 V max. (switch closed; LED on) @ 2 mA sinking
2.7 V min. (switch open; LED off) @ 0.4 mA sourcing
<0.5 V max. (switch open; LED on) @ 2 mA sinking
2.7 V min. (switch closed; LED off) @ 0.4 mA sourcing
250 V
5 VDC (±0.25) @ 25 mA nom.
1
8 msec typical
8 msec typical
4000 V AC/DC
0 °C to 70 °C, operating
-30 °C to 85 °C, storage
Typical switches for use with these modules are switched status
sensors (level sensors, pressure indicators, etc.), magnetic reed
switches (used on doors or windows for burglar alarms), snap-
action micro switches, the auxilliary switches on motor starters, and
most relay contacts.
CAUTION: G4IDC5-SW and G4IDC5-SWNC inputs are not intended
to be used with contacts that are connected to any external user-
supplied voltage or currents.
G4 Digital DC Input Modules