B4 OPTO 22, B4 Datasheet - Page 4

no-image

B4

Manufacturer Part Number
B4
Description
Solid State Relays, Accessories
Manufacturer
OPTO 22
Type
Processr
Datasheets

Specifications of B4

Accessory Type
32 Position Digital Mounting Board
Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Supply Voltage
5V
Mounting Type
Rack
Number Of Channels
32
Power Source
5
For Use With
Pamux Protocol
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
DATA SHEET
Form 737-050801
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Setting the Jumpers
and 8 determine the behavior of the reset line.
Jumpers 1–4 (Address)
eight bits wide, the B4 must be accessed as four consecutive banks of eight I/O channels each. Each bank has its own address.
address plus one; the bank 2 address is the base address plus two; and the bank 3 address is the base address plus three. Hence, only the
base address needs to be configured. Refer to Table 1 to determine how to set this base address.
Figure 6 shows the vertical dimensions of the B4 mounted on either rack.
The B4 includes eight jumpers. Jumpers 1 through 4 set the address, jumpers 5 and 6 set the watchdog functionality, and jumpers 7
These jumpers configure the base address of the B4. Since the brain board controls 32 points of I/O, while the Pamux data bus is only
The four banks on the B4 have contiguous addresses. The bank 0 address is the base address of the B4; the bank 1 address is the base
© 2004 Opto 22. All rights reserved. All trademarks, trade names, logos, and service marks referenced herein belong to their respective companies.
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: sales@opto22.com
Figure 6: Vertical Dimensions of the B4 Mounted on a Rack
B4 INSTALLATION NOTES
BRAIN BOARDS
CLASSIC PAMUX
page 4/9