N6600Z2100-00 WEST INSTRUMENTS, N6600Z2100-00 Datasheet

no-image

N6600Z2100-00

Manufacturer Part Number
N6600Z2100-00
Description
CONTROLLER, TEMPERATURE
Manufacturer
WEST INSTRUMENTS
Datasheet

Specifications of N6600Z2100-00

Thermocouple Type
B, J, K, L, N, R, S, T
Operating Temperature Max
50°C
Operating Temperature Min
0°C
Output Voltage Max
240VAC
Output Voltage Min
120V
Accuracy
±0.25% Of Input Scan
Approval Bodies
CE
Lead Free Status / RoHS Status
na
West 6600 1/16 DIN Plastics Controller
Technical Data
Features
Control Types
Soft Start
Auto/Manual
Output Configuration
Process Alarm Types
Heater Break Alarm Types
Human Interface
PC Configuration
Input
Thermocouple
RTD
Impedance
Accuracy
Sampling
Sensor Break Detection
Heater Current
Outputs & Options
Control & Alarm Relays
Control SSR Outputs
Solid State (Triac) Outputs
Retransmit Outputs
Communications
Dual SP/Current Transfer
Operating & Environmental
Temperature & RH
Power Supply
Front Panel Protection
Approvals and Certification
Full PID with Pre-tune, Self-tune, Manual Tuning, or On-Off control. Heat only or heat & cool
Allows lower SP value and cycle time during the process start-up phase
Selectable from front panel, with bumpless transfer. Instant power-off feature also available
as standard
Up to 4 total. Max 2 for control (Heat & Cool), max 3 for Alarms,
max 1 for retransmit Process value or Setpoint
Process high, process low, SP deviation, band, logical OR
Current low or high, (in absolute amps or % of nominal current) plus contactor/thyristor short
circuit
4 button operation, dual 4 digit 10mm & 8mm high LED displays, plus 3 LED indicators for
alarms, tuning and set-up
Off-line configuration from serial port if RS485 option is fitted.
J, K, R, S, T, B, L, & N.
3 Wire PT100, 50Ω per lead maximum (balanced)
>100MΩ
+/- 0.25% of input span +/- 1 LSD (T/C CJC better than 0.7°C)
4 per second, 14 bit resolution approximately
<2 secs, control O/P’s turn off, high alarms activate for thermocouple ranges, low alarms
activate for RTD
0-50mA secondary from external current transformer. Display is scaleable up to 100 amps
Contacts *SPDT 2Amp resistive at 240V AC,>500,000 operations.
(Dual relay=SPST for O/P’s 2 & 4)
Drive capability, output 1>10V DC into 500Ω min, output 2>4.2V DC into 250Ω min
0.01 to 1 Amp AC 20 to 280V, 47 to 63Hz
0-20/4-20mA into 500Ω max, 0-10/0-5V into 500Ω min. Accuracy typically +/- 0.25%
2 Wire RS485, 1200 to 9600 Baud, Modbus or West ASCII (Selectable)
Volt free or TTL input. Selects between 2 setpoints or quick transfer of heater current as
nominal value
0 to 55°C (-20 to 80°C storage), 20% to 95%RH non-condensing
100 to 240V 50/60Hz 7.5VA (optional 20 to 50V AC 7.5VA/22 to 65V DC 4W)
IEC IP66 (Behind panel protection is IP20)
CE, UL & ULc
The West 6600 provides high quality control in applications requiring
a heater break function or soft-start for process warm up. Heater
current can also be displayed, removing the need for a separate
ammeter.
Heat/Cool operation
Process & Heater alarms
Current “Quick Transfer”
RS485 comms
Product Specification
Soft Start
Ramping setpoint
Current Display

Related parts for N6600Z2100-00

N6600Z2100-00 Summary of contents

Page 1

West 6600 1/16 DIN Plastics Controller Technical Data Features Control Types Full PID with Pre-tune, Self-tune, Manual Tuning, or On-Off control. Heat only or heat & cool Soft Start Allows lower SP value and cycle time during the process start-up ...

Page 2

... Dual SP or Current Transfer/24-48V line West Instruments is a division of Danaher (UK Industries) Ltd. A member of the Danaher Corporation. Registered in England No 2815444 VAT No GB788620583 Registered Office: Danaher House, Parkway One Business Centre, Parkway Drive, Sheffield, S9 4WU e-mail: info@westinstruments.com Web: www.westinstruments.com Cut out 45 x 45mm 45 x 45mm +0.5 – ...

Related keywords