CPM2C-10C1DR-D Omron, CPM2C-10C1DR-D Datasheet - Page 15

Micro Programmable Logic Controller

CPM2C-10C1DR-D

Manufacturer Part Number
CPM2C-10C1DR-D
Description
Micro Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CPM2C-10C1DR-D

Output Type
Relay
External Width
33mm
Supply Voltage Max
24VDC
External Depth
65mm
Mounting Type
DIN Rail
External Height
90mm
Approval Bodies
UL, CSA, CE
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
J DEDICATED I/O MODULES SPECIFICATIONS
Mixed Analog I/O Module CPM2C-MAD11 (2 input and 1 output channels)
For process input variables such as pressure, flow, and humidity,
use a Mixed Analog I/O Module. The single analog output can
provide a signal for recording devices, valve controllers or a
transfer output of the analog signal. Up to 4 Mixed Analog I/O
Modules can be used in a CPM2C system with other Expansion
I/O Modules. A maximum of 5 Expansion I/O Modules, including
Dedicated I/O Modules, can be used in a CPM2C system.
Item
Analog
i
input
section
Analog
output
section
Conversion time
Isolation method
A--106
t
t
t
g
g
Number of inputs
Input signal range
Max. rated input
External input impedance
Resolution
Overall accuracy
A/D conversion data
Averaging function
Open-circuit detection function
Number of outputs
Output signal range
Allowable external output load resistance
External output impedance
Resolution
Overall accuracy
Set data (D/A conversion)
Micro Programmable Controller
y
y
25°C
0 to 55°C
25°C
0 to 55°C
CPM2C
Voltage I/O
2 inputs (2 words allocated)
0 to 10 VDC, or --10 to +10 VDC
±15 V
1 MΩ min.
1/6000 (full scale)
0.3% full scale
0.6% full scale
16-bit binary (4-digit hexadecimal)
Full scale for --10 to +10 V:
Full scale for other ranges:
Supported (Settable for individual inputs via DIP switch)
Supported
1 output (1 word allocated)
1 to 5 VDC, 0 to 10 VDC, or
1 kΩ min.
0.5 Ω max.
1/6000 (full scale)
0.4% full scale
0.8% full scale
16-bit binary (4-digit hexadecimal)
Full scale for --10 to +10 V:
Full scale for other ranges:
2 ms/point (6 ms/all points)
Photocoupler isolation between analog I/O terminals and internal circuits. No
isolation between analog I/O signals.
--10 to +10 VDC
0 to 5 VDC, 1 to 5 VDC,
3. Expansion I/O
1. Analog I/O terminals
connector (input)
2. Input type and
range selector
DIP switch
F448 to 0BB8 Hex
0000 to 1770 Hex
F448 to 0BB8 Hex
0000 to 1770 Hex
Current I/O
0 to 20 mA or 4 to 20 mA
±30 mA
250 Ω
0.4% full scale
0.8% full scale
0 to 20 mA or 4 to 20 mA
600 Ω max.

Related parts for CPM2C-10C1DR-D