PMP120 MACROMATIC CONTROLS, PMP120 Datasheet

PHASE MONITORING RELAY, SPDT, 120VAC

PMP120

Manufacturer Part Number
PMP120
Description
PHASE MONITORING RELAY, SPDT, 120VAC
Manufacturer
MACROMATIC CONTROLS
Series
PMPr
Datasheet

Specifications of PMP120

Contact Configuration
SPDT
Phase Type
3 Phase
Power Consumption
3VA
Supply Voltage Max
120VAC
Switching Voltage Max
240VAC
Operating Time Range
1s To 300s
Relay Mounting
Plug In
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
u
u
u
u
u
u
u
u
PHASE MONITOR RELAYS
Phase Loss, Phase Reversal, Phase
Unbalance, and Under/Over Voltage
PMP Series Plug-in
12
www.macromatic.com
Universal voltage range of
208-480V on PMPU
provides the flexibility to
cover a variety of
applications with one unit
Protects against phase loss,
phase reversal, phase
unbalance, undervoltage
and overvoltage
Variety of user-selectable
and adjustable settings for
the ultimate in three-phase
protection
Automatic or Manual Reset
Multi-Color LED indicates
normal condition and
provides fault indication to
simplify troubleshooting
Compact plug-in case
utilizing industry-standard 8
pin octal socket
10A SPDT output contacts
sales@macromatic.com
800-238-7474
(with appropriate socket)
*
n See Pages 81 & 82 for Sockets & Accessories.
The PMP Series Phase Monitor Relays utilize a microprocessor-based design to provide
protection against phase loss, phase reversal, phase unbalance, undervoltage and
overvoltage. The PMPU is a universal voltage product that works on any three-phase
system voltage from 208-480V (a separate 120V version is available). These devices are
designed to be compatible with most Wye or Delta systems. In Wye systems, a connec-
tion to a neutral is not required. PMP Series products protect against unbalanced voltages
or single phasing regardless of any regenerative voltages.
The relay is energized when the phase sequence and all voltages are correct. Any one of
five fault conditions will de-energize the relay. As standard, re-energization is automatic
upon correction of the fault condition. Manual reset is available if a momentary N.C.
switch is wired to the appropriate terminals. A multi-color LED indicates normal condition
and also provides specific fault indication to simplify troubleshooting.
The PMP Series offers a variety of user-adjustable settings. The percent phase unbalance
is adjustable from 2-10%, and also has a “Disable” setting for those applications where
poor voltage conditions could cause nuisance tripping. The undervoltage drop-out can be
set at 80-95% of operating voltage (overvoltage setting is fixed at 110% of nominal). The
adjustable time delay drop-out on undervoltage (0.1-20 seconds) eliminates nuisance
tripping caused by momentary voltage fluctuations. There is also an adjustable time delay
(1-300 seconds) on both power up and restart after a fault has been cleared.
Requires a 600V-rated socket when used on system voltages greater than 300V.
MOUNTING
Plug-in
STYLE
OPERATING
208-480V
VOLTAGE
50/60 Hz
120V
PRODUCT
NUMBER
PMP120
PMPU *
WIRING/SOCKET n
DIAGRAM 104
8 Pin Octal
70169-D
1/09

Related parts for PMP120

PMP120 Summary of contents

Page 1

... OPERATING MOUNTING VOLTAGE STYLE 50/60 Hz Plug-in 120V 208-480V * Requires a 600V-rated socket when used on system voltages greater than 300V. n See Pages 81 & 82 for Sockets & Accessories. PRODUCT WIRING/SOCKET n NUMBER PMP120 8 Pin Octal 70169-D PMPU * DIAGRAM 104 1/09 ...

Page 2

... Overvoltage Fixed Time Based on Inverse Time Curve Dimensions 2.4 (60) 1/09 PHASE MONITOR RELAYS Phase Loss, Phase Reversal, Phase Unbalance, and Under/Over Voltage Application Data & Dimensions Hysteresis Load (Burden): Less than 3VA Temperature: -28 Mounting: Uses an 8 pin octal socket. Requires a 600V-rated socket when used on system voltages greater than 300V (Macromatic Product Number 70169-D--see Page 81) ...