PAP240 MACROMATIC CONTROLS, PAP240 Datasheet - Page 2

PHASE MONITORING RELAY, SPDT, 240VAC

PAP240

Manufacturer Part Number
PAP240
Description
PHASE MONITORING RELAY, SPDT, 240VAC
Manufacturer
MACROMATIC CONTROLS
Series
PAPr
Datasheet

Specifications of PAP240

Contact Configuration
SPDT
Phase Type
3 Phase
Power Consumption
3VA
Supply Voltage Max
240VAC
Switching Voltage Max
240VAC
Operating Time Range
50ms
Relay Mounting
Plug In
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Application Data
Phase Loss:
Unit trips on loss of any Phase A, B or C
Phase Reversal:
Unit trips if sequence of the three phases is anything other than A-B-C.
Undervoltage:
Adjustable over a range per product selection table. Unit trips when the average of all three lines is less than the
adjusted set point.
Output Contacts:
10A Resistive SPDT @ 240V AC, 1/3HP @ 120/240V AC (N.O.), 1/6HP @ 120/240V AC (N.C.)
Life:
Full Load: 100,000 operations
Response Times:
Operate: 50ms
Release: 50ms
Load (Burden):
3VA
Temperature:
Transient Protection:
10,000 volts for 20 microseconds
Mounting:
Uses an 8 pin octal socket. Requires a 600V-rated socket when used on system voltages greater than 300V (Macromatic
Product Number 70169-D--see Page 81).
Indicator LED:
Red LED on when all conditions are normal, and off when a fault condition has occurred.
Reset:
Automatic upon correction of fault
Approvals:
Dimensions
-28
1/09
o
to 65
o
C (-20
File #E109466
o
to 150
2.4 (60)
o
F)
File #E109466
with
appropriate
socket
(43)
Phase Loss, Phase Reversal & Undervoltage
1.7
PHASE MONITOR RELAYS
Inches (Millimeters)
All Dimensions in
(74)
2.9
Application Data & Dimensions
(89)
3.5
PAP Series Plug-in
11

Related parts for PAP240