289E Hammond Manufacturing, 289E Datasheet - Page 3

Transformers 750VA PLUG IN ISOL

289E

Manufacturer Part Number
289E
Description
Transformers 750VA PLUG IN ISOL
Manufacturer
Hammond Manufacturing
Type
Power Transformersr
Datasheet

Specifications of 289E

Power Rating
750 VA
Primary Voltage Rating
240 V
Secondary Voltage Rating
120 V
Dimensions
10.25 in L x 7.5 in W x 5 in H
Product
Power Transformers
Height
5 in
Length
10.25 in
Number Of Outputs
1
Termination Style
Plug In
Width
7.5 in
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Straight Isolation
through careful design, but these units are NOT usable in an office environment.
AC regulating - protects against both brownouts & over voltage conditions.
Protects against any power problem other than a blackout.
Will operate through a 3 millisecond (minimum) blackout.
Long life - ferroresonant design - no moving parts.
Ferroresonant design also filters out surges, line harmonics, and RF noise.
Input 120VAC (+10 % to -25 %), 60 Hz
Output 120VAC (+/- 3 %).
Provides circuit isolation.
Noise Isolation (RF) of 120 db common mode, 60 db normal mode.
Spike attenuation: 250:1 minimum.
Sine wave output - total harmonic distortion (THD): 3 %
Units also include a 2nd stage of high frequency filtering on the output - a Hammond Mfg. exclusive.
Operating temperature range of -40 degrees C to +40 degrees C.
Standard 3-wire, grounded plug & receptacle.
Front panel lighted power switch.
Input (primary) connected to an extra long 15 foot, heavy duty 14/3 SJTW cord for extreme temperature ranges.
Integral molded, standard North American plug (NEMA 5-15P).
Output (secondary) connected to a rear mounted, standard North American, grounded receptacle (NEMA 5-15R) -
quantity depends on power capacity of unit (see table below).
Rugged two piece ventilated steel enclosure.
Finished in a grey/beige color, textured powder paint with rubber feet installed.
NOTE 1: Due to the nature of ferroresonant designs - these units do produce audible noise. We have reduced this
NOTE 2: These units provide complete isolation from the source voltage. In other words, the "neutral" output wire has
no connection to ground, this is a UL requirement for this type of device. Therefore plug-in circuit testers
& line "polarity" testing devices will NOT function on the output as it is completely isolated.
North American Mark of Safety: C UL & UL listed (File #E211544).
©
St. Laurent, Quebec (514) 343-9010
Cheektowaga, NY (716) 630-7030
Guelph, Ontario (519) 822-2960
CANADA
USA
CV1201200
CV1201800
CV120300
CV120600
Part No.
- Constant Voltage - Plug In (CV Series)
1200
1800
300
600
VA
Capacity
(RMS)
Amps
A.C. Regulator - Plug In
www.hammondmfg.com
2.5
10
15
5
(120 V to 120V)
Constant Voltage
Rear Outlets
Number of
2
4
4
6
60
Height
12.00
7.00
9.00
9.00
Dimensions (Inches)
Width
10.13
10.13
12.13
7.13
Depth
12.30
19.50
19.50
20.50
Queenstown, Australia 61-8-8240-2244
Basingstoke, UK 01256 812812
Lbs.
25.3
Wt.
48
74
95
AUSTRALIA
EUROPE

Related parts for 289E