EDS11-160C FUJI [Fuji Electric], EDS11-160C Datasheet
EDS11-160C
Related parts for EDS11-160C
EDS11-160C Summary of contents
Page 1
... Withstand voltage: Power source all terminals 1500 V AC for 1 min Relay contact output 1500 V AC for 1 min Between others 500 V AC for 1 min (5) Approvals and certification: UL(UL873), C-UL(CSA C22.2 No.24-93 or equivalent), CE mark(LVD : EN61010-1, EMC : EN61326-1) PXG9 all terminals EDS11-160c Date Apr. 1, 2011 ...
Page 2
PXG9 2. Input section 2.1 Process value input (1) Number of inputs: 1 point (2) Input setting: Programmable scale (3) Input signal: See Table 1 (thermocouple, resistance bulb, mV, voltage, current(With external 250 resistance) universal input) (4) Standard measurement range ...
Page 3
Output section 3.1 Control output (1) Number of points points (2 points: Heating/cooling control) (2) Type: selected out of [1] to [5] below [1] Relay contact output • Proportional cycle 150 sec • Contact ...
Page 4
PXG9 4. Indication/setting section 4.1 Display unit (1) Type: LED (2) Indication contents: Process value indication: 7 segments, 4 digits [red] Setpoint indication: 7 segments, 4 digits [green] Indication status: 6 indicator lamps 4.2 Setting section (1) Type: Sheet type ...
Page 5
Structure (1) Mounting method: Mounted with panel (2) External terminals: Screw terminals, M3 (3) Case: • Material: ABS, and degeneration PPO • Non-combustibility grade: UL94V-0 equivalent • Color: Black (4) Protection structure: • Panel front side: IP66, NEMA-4X equiva- ...
Page 6
PXG9 CODE SYMBOLS Standard type Digit Specifications 4 <Front panel size W H> 96 96mm 5 <Output 1> Relay contact SSR drive Current ( DC DC) Voltage ( DC ...
Page 7
CODE SYMBOLS Motorized valve control type Digit Specifications 4 <Front panel size W H> 96 96mm 5 <Output 1> Motorized valve control output (Without PFB) Motorized valve control output (With PFB) 6 <Output 2> None Auxiliary Digital output Transmitter power ...
Page 8
PXG9 OPTIONALLY ITEMS Instruction manual for communication functionRS485 (Modbus) Current detector for heater burnout alarm Rear terminal cover Shunt resistor 250 0.1% PC loader communication cable TABLE 1 [1] Unit of temperature: ˚C Input Input type code 0 JPt100 Resistance ...
Page 9
OUTLINE DIAGRAM (Unit : mm) 96 Water-proof packing 37-48 49-60 61-72 1-12 13- Rear view Mounting bracket 94.5 (terminal cover included Panel PC loader ...
Page 10
PXG9 OPTIONALLY ARRANGED ARTICLES Heater current detector (CT) . Specification : Type : CTL-6-S 5 Note 1) Detection is available only for single phase heater. Note 2) Unusable for heater control ...
Page 11
EXTERNAL CONNECTION DIAGRAM Standard type with communication OPTION1 RS485,DI1,RSV1,CT1 RS485+DI+RSV1 RS485+RSV1/RS485+CT1/RS485+ RS485 RS485 RS485 2 2 DI1 3 3 RSV1 CT1 4 DI-COM 4 5 RSV1 6 TOP TOP ...
Page 12
PXG9 Standard type without communication OPTION 1 DI1,DI2,RSV1,CT1 DI1+DI2+RSV1 DI1+RSV1/DI1+CT1/DI1+DI2 DI1 1 1 DI1 DI- DI-COM 2 2 COM DI2 3 3 RSV1 RSV1 6 TOP TOP PS Power supply DO DO1- COM DO1 11 11 DO2- ...
Page 13
Motorized valve control type with communication OPTION 1 RS485,DI1,DI2,DI3,RSV1 RS485+DI+RSV1 RS485+DI1+DI2+DI3 1 RS485 RS485 2 DI1 DI1 3 DI-COM 4 DI-COM DI2 5 RSV1 6 DI3 TOP TOP PS Power supply DO DO1- COM DO1 11 11 DO2 ...
Page 14
PXG9 Motorized valve control type without communication OPTION 1 DI1,DI2,DI3,RSV1 DI1+DI2+DI3+RSV1 DI1 DI- COM DI2 DI3 RSV1 TOP TOP PS Power supply DO DO1- COM DO1 11 11 DO2 COM DO2 100-240VAC 24VAC/24VDC 50/60Hz 50/60Hz ...
Page 15
ISOLATED BLOCK DIAGRAM Power supply Control output 1 (relay contact) or OPEN output Control output 2 (relay contact) or CLOSE output Digital output 1 (relay contact) Digital output 2 (relay contact) When the 9th digit of the code symbols = ...
Page 16
PXG9 ...