XTOB040DC1 EATON CUTLER HAMMER, XTOB040DC1 Datasheet - Page 116
XTOB040DC1
Manufacturer Part Number
XTOB040DC1
Description
Overload Relay
Manufacturer
EATON CUTLER HAMMER
Datasheet
1.XTCE007B10A.pdf
(312 pages)
Specifications of XTOB040DC1
Overload Adjustment Current Min
24A
Overload Adjustment Current Max
40A
Coil Voltage Dc Max
220V
Coil Voltage Vdc Nom
220V
For Use With
Eaton Cutler-Hammer Frame D XT Series 40-65A Contactors
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
- Current page: 116 of 312
- Download datasheet (6Mb)
34-116
34
Technical Data and Specifications
Table 34-142. Overload Relay Specifications
Protection
Trip Class
Reset
Indications
PCBA
Options
General
Description
Thermal
Phase Loss
Phase Imbalance
Inrush Current
Class 5, 10, 20, 30
M / M-O
A / A-O
Test Indicator
Trip Indicator
Power Sensing
Instant Reset by Power ON
Thermal memory
Cold and Hot Trip Curves
Power Consumption
Safety Cover
Remote Reset
IEC Contactors & Starters
XT IEC Power Control
Overload Relays — C396
C396_2_
Standard
1.05 x FLA: Does not trip
1.25 x FLA: Overload trip
1 Phase = 0, Trip time = 3s (Hot Status)
Max - Min / Max > 40%,
Trip time = 3s (Hot Status)
> 8 x Max FLA, Trip time is 0.3s (Cold Status)
Manual / Manual + Stop
Auto / Auto + Stop
Auto Reset Time = 165s
Yellow
Yellow
3 phase
CPU reset by Power ON after 2 – 3s
< 3 min.
Power ON > 20 min. is Hot Status
< 300 mW
Covers FLA dial, DIP switches
24V DC, 24V AC, 120V AC, 240V AC
Selectable
For more information visit: www.eaton.com
Overload Relay Specifications (Continued)
Climate Considerations
Voltages
FLA Range
Safety
Capacity
Load Terminal Capacity
Load Terminal Tightening Torque in Nm (lb-in)
General Description
Ambient Temperature
(Operating)
Ambient Temperature
(Storage / Transportation)
Humidity
Altitude (Operating)
Pollution (Operating —
External)
Mechanical Shock
Resistance
(IEC/EN 68-2-17)
Vibration (Lloyd’s Register
of Shipping, Vibration Test
2)
Temperature
Compensation
Control Voltage
Insulation Voltage (Ui) —
Main Circuit
Insulation Voltage (Ui) —
Control Circuit
Impulse Withstand Voltage
(Uimp) VAC
45 mm Frame: C396A_
65 mm Frame: C396B_
110 mm Frame: C396C_
Degree of Protection
Control Terminal Capacity
Control Terminal Tightening
Torque in Nm (lb-in)
45 mm Frame: C396A_
65 mm Frame: C396B_
110 mm Frame: C396C_
45 mm Frame: C396A_
65 mm Frame: C396B_
110 mm Frame: C396C_
Dimensions . . . . . . . . . . . . . . Pages 34-117, 34-118
C396_2_
Standard
-25° to 65°C (-13° to 149°F) inside enclosure
-40° to 80°C (-40° to 176°F)
UL991 (H3): 20 – 95% non-condensing
NEMA ICS1: 2000 meters max above sea
level
Pollution degree 3
15g
Continuous
12 – 690V AC, 50/60 Hz
1000V AC
690V AC
6000
0.1 – 45A
15 – 110A
30 – 150A
IP20 (Stand-Alone Version Only)
18 – 14 AWG
0.79 (7)
14 – 6 AWG
10 – 1 AWG
6 AWG – 250 mcm
3.2 (28)
9.0 (80)
22.6 (200)
6g
CA08102001E
March 2009
Related parts for XTOB040DC1
Image
Part Number
Description
Manufacturer
Datasheet
Request
R
Part Number:
Description:
PROGRAMMABLE LOGIC CONTROLLER
Manufacturer:
EATON CUTLER HAMMER
Part Number:
Description:
Pm Power Pro 3000/5000 A-B Accel/On Interface
Manufacturer:
EATON CUTLER HAMMER
Part Number:
Description:
Handle Tie Bar For (2) - 1 Pole Type BR Breakers
Manufacturer:
EATON CUTLER HAMMER
Part Number:
Description:
Type CH Breaker 150A/2 Pole 120/240V 10K
Manufacturer:
EATON CUTLER HAMMER
Part Number:
Description:
Tenant Branch Breaker 125A/3 Pole 120/240V 42K
Manufacturer:
EATON CUTLER HAMMER
Part Number:
Description:
Type CL Breaker 25A/1Pole 120/240V 10K-Classified 1" Ckt Bkr
Manufacturer:
EATON CUTLER HAMMER
Part Number:
Description:
FD BREAKER 1P 80 AMP WITH LOAD ONLY TERMINALS
Manufacturer:
EATON CUTLER HAMMER
Part Number:
Description:
GD 2 POLE BREAKER, 25 AMP, SINGLE PACKED
Manufacturer:
EATON CUTLER HAMMER
Part Number:
Description:
Handle Tie Bar For (2) - 1 Pole Type BR Breakers
Manufacturer:
EATON CUTLER HAMMER
Part Number:
Description:
Type CL Breaker 25A/1Pole 120/240V 10K-Classified 1" Ckt Bkr
Manufacturer:
EATON CUTLER HAMMER